Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 92

84
9424200892 Rev F
Description
Value / Clarification
What is the fast retransmission scheme?
Is it fixed or configurable?
1) 4 msec with TAL = 8 msec
2) 8 msec with TAL = 16 msec
3) 16 msec with TAL = 32 msec
4) 32 msec with TAL = 64 msec
5) 64 msec with TAL = 128 msec
6) 128 msec with TAL = 256 msec Fixed
Can the Goose publish be turned on / off by using
SetGoCBValues(GoEna)
Y
TAL = Time Allowed to Live
Table 28. PIXIT for Control Model
Description
Value / Clarification
What control modes are supported?
(compare PICS)
Y status-only (XCBR)
Y direct-with-normal-security (CTLGGIO)
N sbo-with-normal-security
N direct-with-enhanced-security
N sbo-with-enhanced-security
Is the control model fixed, configurable and/or
online changeable?
Fixed
Is Time activated operate (operTm) supported?
N
Is “operate-many” supported?
N
What is the behavior of the DUT when the test
attribute is set in the SelectWithValue and/or
Operate request?
DUT ignores the test value and executes the
command as usual
What are the conditions for the time (T) attribute
in the SelectWithValue and/or Operate request?
DUT ignores the time value and executes the
command as usual
Is pulse configuration supported?
N
What is the behavior of the DUT when the check
conditions are set?
Is this behavior fixed, configurable, online
changeable?
N synchrocheck
N interlock-check
DUT ignores the check value and always perform
the action
Fixed
What additional cause diagnosis are supported?
N Blocked-by-switching-hierarchy
N Select-failed
N Invalid-position
N Position-reached
N Parameter-change-in-execution
N Step-limit
N Blocked-by-Mode
N Blocked-by-process
N Blocked-by-interlocking
N Blocked-by-synchrocheck
N Command-already-in-execution
N Blocked-by-health
N 1-of-n-control
N Abortion-by-cancel
N Time-limit-over
N Abortion-by-trip
How to force a “test-not-ok” respond with
SelectWithValue request?
n/a
Conformance Statements
BE1-11