Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 93

9424200892 Rev F
85
Description
Value / Clarification
How to force a “test-not-ok” respond with Select
request?
n/a
How to force a “test-not-ok” respond with Operate
request?
DOns: Operate is always possible
SBOns: not supported
DOes: not supported
SBOes: not supported
Which origin categories are supported?
DOns: All
SBOns: not supported
DOes: not supported
SBOes: not supported
What happens if the orCat is not supported?
no action
Does the IED accept an selectwithvalue/operate
with the same ctlVal as the current status value?
DOns: Yes
SBOns: not supported
DOes: not supported
SBOes: not supported
Does the IED accept a select/operate on the
same control object from 2 different clients at the
same time?
DOns: Yes
SBOns: not supported
DOes: not supported
SBOes: not supported
Does the IED accept a select/selectwithvalue from
the same client when the control object is already
selected (tissue 334)
n/a
Is for SBOes the internal validation performed
during the SelectWithValue and/or Operate step?
n/a
Can a control operation be blocked by Mod=Off or
Blocked?
N
Does the IED support local / remote operation?
N
Table 29. PIXIT for Time and Time Synchronization Model
Description
Value / Clarification
What quality bits are supported?
N LeapSecondsKnown
N ClockFailure
Y ClockNotSynchronized
Describe the behavior when the time
synchronization signal/messages are lost
continues to use internal clock
When is the time quality bit "Clock not
synchronized” set?
when SNTP is not configured or SNTP lost sync
Is the timestamp of a binary event adjusted to the
configured scan cycle?
N
Does the device support time zone and daylight
saving?
Y
Which attributes of the SNTP response packet are
validated?
N Leap indicator not equal to 3?
Y Mode is equal to SERVER
N OriginateTimestamp is equal to value sent by
the SNTP client as Transmit Timestamp
N RX/TX timestamp fields are checked for
reasonableness
Y SNTP version 4
N other (describe)
BE1-11
Conformance Statements