Signal identification, Ied related naming – Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 16

10
9424200892 Rev F
Signal Identification
Elements of the signal identification as defined in IEC 61850–7–2 are illustrated in Figure 7.
Figure 7. Elements of the Signal Identification as Defined in IEC 61850-7-2
The signal designation consists of the following four parts:
1.
A user defined part identifying the Logical Device LD in the process (LDName).
2.
A function related part to distinguish several LNs of the same class within the same LD/IED (LN-
Prefix).
3.
The standardized LN class name and the LN instance number, which distinguishes several LNs
of the same class and prefix within the same LD/IED.
4.
A signal identification inside a LN consisting of data and attribute name as defined in IEC 61850–
7–3 and IEC 61850–7–4.
IED Related Naming
The LDName part is built out of the objects IED and LDevice. The LNName is the LN Prefix, the LN class
and the LN instance #.
The LN prefix is used to identify several versions of a LN class. The link between the IED and the primary
process (Substation, Voltage level, Bay) is given in the substation section of the station SCD file but not in
the signal identification in the telegram. The IED name may be extended with a short form of the three
missing levels. See Figure 8.
LDName
LN Prefix
LN Class
LN Instance #
Data Name
Data Attribute Name
Defined in IEC
61850-7-4
Defined in IEC
61850-7-3
Configurable
LNName
P0061-62
Part 1
Part 2
Part 3
Part 4
BE1_11PRO
IND
GGIO
1
Ind01
stVal
LNName
BE1-11 XML Example: BE1_11PRO.INDGGIO1$Ind01$stVal
IEC 61850 Engineering
BE1-11