Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 90

82
9424200892 Rev F
Table 24. PIXIT for Data Set Model
Description
Value / Clarification
What is the maximum number of data elements in
one data set (compare ICD setting)?
Not limited by an internal configuration parameter.
It depends on the available memory.
How many persistent data sets can be created by
one or more clients?
There are up to 16 pre-defined (configured) data
sets for each LD. Persistent data sets are not
supported.
How many non-persistent data sets can be
created by one or more clients?
Not supported
Table 25 . PIXIT for Setting Group Control Model
Description
Value / Clarification
What is the number of supported setting groups
for each logical device (compare NumSG in the
SGCB)?
4 (Selection of group only, Editing not supported)
What is the effect of when and how the non-
volatile storage is updated?
(compare IEC 61850-8-1 $16.2.4)
n/a
Can multiple clients edit the same setting group?
n/a
What happens if the association is lost while
editing a setting group?
n/a
Is EditSG value 0 allowed?
n/a
Table 26. PIXIT for Reporting Model
Description
Value / Clarification
The supported trigger conditions are
(compare PICS)
integrity
data change
quality change
data update
general interrogation
Y
The supported optional fields are
sequence-number
report-time-stamp
reason-for-inclusion
data-set-name
data-reference
buffer-overflow
entryID
conf-rev
segmentation
Can the server send segmented reports?
Y
Mechanism on second internal data change
notification of the same analogue data value
within buffer period (Compare IEC 61850-7-2
$14.2.2.9)
Send report immediately
Multi-client URCB approach
(compare IEC 61850-7-2 $14.2.1)
All client can access all URCB’s
What is the format of EntryID?
Octet string 8
What is the buffer size for each BRCB or how
many reports can be buffered?
1,000,000 bytes for all report control blocks.
More than 200 rcb blocks
Conformance Statements
BE1-11