Pics – Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 83

9424200892 Rev F
75
BE1-11f
BE1-11i
BE1-11g
BE1-11t
BE1-11m
Z: Other
Motor: ZMOT
Output
Logic Point
PICS
The following ACSI conformance statements are used to provide an overview and details about the
BE1-11 Protection System.
•
ASCI basic conformance statement (Table 19)
•
ACSI models conformance statement (Table 20)
•
ACSI service conformance statement (Table 21)
The statements specify the communication features mapped to IEC 61850-8-1.
Table 18. Conformance Statement Key and Notes
Table Entry
Description
Yes
Supported with MMS services and objects necessary for implementing this capability.
No
Not supported.
Not applicable.
Table 19. ACSI Basic Conformance Statement
Client/subscriber Server/publisher Value/comments
CLIENT-SERVER ROLES
B11 Server side (of two-party
application-association)
c1
Yes
B12 Client side (of two-party
application-association)
c1
No
SCSMS SUPPORTED
B21 SCSM: IEC 61850-8-1 used
Yes
B22 SCSM: IEC 61850-9-1 used
No
B23 SCSM: IEC 61850-9-2 used
No
B24 SCSM: other
No
GENERIC SUBSTATION EVENT MODEL (GSE)
B31 Publisher side
O
Yes
B32 Subscriber side
O
Yes
TRANSMISSION OF SAMPLED VALUE MODEL (SVC)
B41 Publisher side
O
No
B42 Subscriber side
O
No
Notes:
c1 - shall be 'M' if support for LOGICAL-DEVICE model has been declared.
O - Optional
M - Mandatory
BE1-11