Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 82

74
9424200892 Rev F
BE1-11f
BE1-11i
BE1-11g
BE1-11t
BE1-11m
Overvoltage : PTOV1, PTOV2, PTOV3, PTOV4
59P-1 to 4
59P-1 to 4
59P-1 to 4
59P-1 to 4
59P-1 to 2
Overvoltage : PTOV5, PTOV6, PTOV7, PTOV8
59X-1 to 4
59X-1 to 4
59X-1 to 4
59X-1 to 4
59X-1 to 2
Motor Restart Inhibition: PMRI1
66
Phase Angle Measuring: P78VPPAM1
78V
78V
Phase Angle Measuring:P78OOSPPAM1
78OOS
Under Frequency : PTUF1, PTUF2, PTUF3, PTUF4
81-1 to
81-4
81-1 to
81-4
81-1 to
81-4
81-1 to
81-4
81-1, 81-2
Over Frequency : PTOF1, PTOF2
81-5, 81-6
81-5, 81-6
81-5, 81-6
81-5, 81-6
Over Frequency : PTOF3, PTOF4
81-3 , 81-4
Rate Of Change Frequency : PFRC1, PFRC2
81-7, 81-8
81-7, 81-8
81-7, 81-8
81-7, 81-8
Differential protection: P87NPDIF1
87N
optional
87N-1,
87N-2
Differential protection: P87PDIF1
87 optional
87
87 optional
Protection Trip Conditioning : PTRC1
Logic
Points
Logic
Points
Logic
Points
Logic
Points
Logic
Points
R: Protection related functions
Sync-check : RSYN1
25
25
25 optional
Auto synchronizer: P25ARSYN1
25A
optional
Breaker failure : RBRF1
50BF
50BF
50BF
50BF
50BF
Automatic reclosing : RREC1
79
79
Fault locator : RFLO1
FLT
FLT
FLT
FLT
FLT
Disturbance Recorder Function: RDRE
FLT
FLT
FLT
FLT
FLT
G: Generic References
Generic Process Control Inputs : CTLGGIO1,
CTLGGIO2, CTLGGIO3, CTLGGIO4
Input
Logic
Points
Input
Logic
Points
Input
Logic
Points
Input
Logic
Points
Input
Logic
Points
Generic Process Indicator Outputs : INDGGIO1,
INDGGIO2, INDGGIO3, INDGGIO4
Output
Logic
Points
Output
Logic
Points
Output
Logic
Points
Output
Logic
Points
Output
Logic
Points
M: Metering and Measurement
Multi-Phase Measurement : MMXU1
CT Circuit 1
Amps,
Volts,
Power,
Freq
Amps,
Volts,
Power,
Freq
Amps,
Volts,
Power,
Freq
Amps,
Volts,
Power,
Freq
Amps,
Volts,
Power,
Freq
Multi-Phase Measurement : IABCMMXU1
CT Circuit 1
Amps
Amps
Amps
Amps
Amps
Multi-Phase Measurement : IABCMMXU2
CT Circuit 2
Amps
optional
Amps
optional
Amps
optional
Amps
Amps
Single Phase Measurement : VXMMXN1
VX
VX
VX
VX
VX
Single Phase Measurement : IGMMXN1
CT Circuit 1
IG or IG1
IG or IG1
IG or IG1
IG or IG1
IG or IG1
Single Phase Measurement : IGMMXN2
CT Circuit 2
IG2
optional
IG2
optional
IG2
optional
IG2
IG2
Sequence Components : MSQI1
CT Circuit 1
I0, I1, I2,
V0, V1, V2
I0, I1, I2,
V0, V1, V2
I0, I1, I2,
V0, V1, V2
I0, I1, I2,
V0, V1, V2
I0, I1, I2,
V0, V1, V2
Sequence Components : MSQI2
CT Circuit 2
I0, I1, I2
I0, I1, I2,
I0, I1, I2
I0, I1, I2
I0, I1, I2
X: Switchgear
Circuit breaker : XCBR1
52a, 52b
Trip &
Close Coil
52a, 52b
Trip &
Close Coil
52a, 52b
Trip &
Close Coil
52a, 52b
Trip &
Close Coil
52a, 52b
Trip &
Close Coil
Conformance Statements