Conformance statements, Mics – Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 81

9424200892 Rev F
73
Conformance Statements
The following conformance statements described in this chapter are applicable for a BE1-11 Protection
System with firmware version 2.08.02:
•
MICS (Model Implementation Conformance Statement)
•
PICS (Protocol Implementation Conformance Statement)
•
PIXIT (Protocol Implementation eXtra Information for Testing)
•
TICS (TISSUES Implementation Conformance Statement)
MICS
This MICS document specifies the modeling extensions compared to IEC 61850 Edition 1. For the exact
details on the standardized model, please compare the ICD substation configuration file: “BE1_11.icd”,
version 3.1.0.0.
Table 17 contains the list of logical nodes implemented in the device.
Table 17. Logical Nodes
BE1-11f
BE1-11i
BE1-11g
BE1-11t
BE1-11m
L: System
Logical node zero: LLN0
LLN0
LLN0
LLN0
LLN0
LLN0
Physical device information: LPHD1
PHYDEV
PHYDEV
PHYDEV
PHYDEV
PHYDEV
P: Protection functions
Distance: PDIS1,PDIS2
21-1, 21-2
Volts Per Hz : PVPH1
24
24
24
Undervoltage : PTUV1, PTUV2, PTUV3, PTUV4,
PTUV5
27P-1 to 5
27P-1 to 5
27P-1 to 5
27P-1 to 5
27P-1 to 4
Undervoltage : PTUV6, PTUV7, PTUV8, PTUV9
27X-1 to 4
27X-1 to 4
27X-1 to 4
27X-1 to 4
Directional Over Power : PDOP1
32-1
optional
32-1
32-1
Directional Under Power : PDUP1
32-2
optional
32-2
32-2
Directional Under Power : PDUP2
32-1
Time Undercurrent: PTUC1
37
Loss of Excitation Reverse Var Based : P40QPDUP1
40Q
40Q
Loss of Excitation Impedance Based : P40ZPDUP1
40Z
Incomplete Sequence: PMSS1
48
Thermal Overload : P49TCPTTR1
49TC
Thermal Overload: P49RTDPTTR1, P49RTDPTTR2,
P49RTDPTTR3, P49RTDPTTR4, P49RTDPTTR5,
P49RTDPTTR6, P49RTDPTTR7, P49RTDPTTR8,
P49RTDPTTR9, P49RTDPTTR10, P49RTDPTTR11,
P49RTDPTTR12, P49RTDPTTR13, P49RTDPTTR14
49RTD-1
to
49RTD-14
49RTD-1
to
49RTD-14
49RTD-1
to
49RTD-14
49RTD-1
to
49RTD-14
49RTD-1
to
49RTD-14
Instantaneous Overcurrent : PIOC1, PIOC2, PIOC3,
PIOC4, PIOC5, PIOC6, PIOC7, PIOC8, PIOC9
50-1 to
50-6
50-1 to
50-6
50-1 to
50-6
50-1 to
50-9
50-1 to
50-6
Time Overcurrent : PTOC1, PTOC2, PTOC3, PTOC4,
PTOC5, PTOC6, PTOC7, PTOC8, PTOC9
51-1 to
51-5
51-1 to
51-5
51-1 to
51-5
51-1 to
51-9
51-1 to
51-5
Voltage Control Overcurrent : PVOC1, PVOC2
51-6, 51-7
51-6, 51-7
51-6, 51-7
Transformer Time Overcurrent: P51TFPTOC1
51TF
Under Power Factor: PUPF1
55
BE1-11
Conformance Statements