Table 30. PIXIT for File Transfer Model
Description
Value / Clarification
What is structure of files and directories?
comtrade files (*.hdr *.cfg *.dat)
LD/
Is the IETF FTP protocol also implemented?
N
Directory names are separated from the file name
by
/ (forward slash)
The maximum file name size including path
(recommended 64 chars)
up to 64 chars
Are directory/file name case sensitive?
case sensitive
Maximum file size
Maximum file size is not defined. Free space
varies and size depends completely on con-
figuration.
Is the requested file path included in the file name
of the MMS fileDirectory respond?
Y
Is the wild char supported MMS fileDirectory
request?
N
Is it allowed that 2 client get a file at the same
time?
N
TICS
This section provides a template for the tissues conformance statement. According to the UCA IUG QAP,
the tissue conformance statement is required to perform a conformance test and is referenced on the
certificate.
Mandatory Intop Tissues
During the October 2006 meeting, IEC TC57 working group 10 decided that:
•
green Tissues with the category “IntOp” are mandatory for IEC 61850 edition 1
•
Tissues with the category “Ed.2” Tissues should not be implemented.
Table 31 gives an overview of the implemented IntOp Tissues.
Table 31. Implemented IntOp Tissues
Part
Tissue Description
Nr
Implemented
Y/n/a
8-1
116
GetNameList with empty response?
Y
165
Improper Error Response for GetDataSetValues
n/a
83
GetNameList error handling
Y
7-4
None
7-3
28
Definition of APC
n/a
54
Point def xVal, not cVal
n/a
55
Ineut = Ires ?
n/a
60
Services missing in tables
n/a
63
mag in CDC CMV
n/a
65
Deadband calculation of a Vector and trigger option
n/a
219
operTm in ACT
n/a
270
WYE and DEL rms values
n/a
Conformance Statements
BE1-11