Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 85

9424200892 Rev F
77
Client/subscriber
Server/publisher
Value/comments
IF SVC (B41/B42) IS SUPPORTED
M14
Multicast SVC
O
O
No
M15
Unicast SVC
O
O
No
M16
Time
M
M
Yes
M17
File transfer
O
O
Yes
Notes:
c2 - shall be 'M' if support for LOGICAL-NODE model has been declared.
c3 - shall be 'M' if support for DATA model has been declared.
c4 - shall be 'M' if support for DATA-SET/Substitution/Report/Log Control/or Time model has been
declared.
c5 - shall be 'M' if support for Report/GSE/or SV models has been declared.
O - Optional
M - Mandatory
Table 21. ACSI Service Conformance Statement
SERVICES
AA:
TP/MC
Client/
subscriber
Server/
publisher
Value/
comments
SERVER
S1
ServerDirectory
TP
M
Yes
APPLICATION ASSOCIATION
S2
Associate
M
M
Yes
S3
Abort
M
M
Yes
S4
Release
M
M
Yes
LOGICAL DEVICE
S5
LogicalDeviceDirectory
TP
M
M
Yes
LOGICAL NODE
S6
LogicalNodeDirectory
TP
M
M
Yes
S7
GetAllDataValues
TP
O
M
Yes
DATA
S8
GetDataValues
TP
M
M
Yes
S9
SetDataValues
TP
O
O
Yes
S10
GetDataDirectory
TP
O
M
Yes
S11
GetDataDefinition
TP
O
M
Yes
DATA SET
S12
GetDataSetValues
TP
O
M
Yes
S13
SetDataSetValues
TP
O
O
No
S14
CreateDataSet
TP
O
O
No
S15
DeleteDataSet
TP
O
O
No
S16
GetDataSetDirectory
TP
O
O
Yes
SUBSTITUTION
S17
SetDataValues
TP
M
M
No
BE1-11
Conformance Statements