Bestcomsplus, Ctlggio oper output and indggio oper input, Ctlggio oper alarm – Basler Electric BE1-11 IEC 61850 Protocol User Manual
Page 23: Iec61850ptrc logic block, Bestcoms plus

9424200892 Rev F
17
BESTCOMSPlus
®
BESTCOMSPlus is a Windows
®-based, PC application that provides a user-friendly, graphical user
interface (GUI) for use with Basler Electric communicating products. BESTCOMSPlus is used to program
IEC 61850 logic. It is also used to program BE1-11 operational settings and other logic. For more
information, refer to the BESTCOMSPlus Software chapter in the appropriate BE1-11 instruction manual
below:
•
9424200990 - Instruction Manual for BE1-11f
•
9424200993 - Instruction Manual for BE1-11i
•
9424200994 - Instruction Manual for BE1-11g
•
9424200995 - Instruction Manual for BE1-11t
•
9424200996 - Instruction Manual for BE1-11m
CTLGGIO OPER Output and INDGGIO OPER Input
The IEC 61850 GGIO IND outputs and OPER inputs in BESTCOMSPlus are used to map BE1-11 inputs
and outputs to IEC 61850 data points. These data points can be read directly with an IEC 61850 browser
such as IED Scout made by Omicron. The GGIO inputs and outputs can be used in an IEC 61850
DataSet which is tied to GOOSE Control Blocks (GoCB) for sending/receiving GOOSE messages.
A CTLGGIO 61850 logic output and INDGGIO logic input are shown in Figure 14.
Figure 14. 61850 Logic Output and Input
CTLGGIO OPER Alarm
The CTLGGIO OPER ALARM is set if the device has subscribed to a GOOSE message, mapped it to the
corresponding CTL GGIO, and the device has not received the subscribed GOOSE message within the
TTL (Time To Live). The TTL for the next reception is included within a GOOSE message. If the TTL timer
expire and the alarm is set, the CTLGGIO OPER logic input will switch over to the default that is
configured within the BE1-11 settings. If the device starts receiving GOOSE messages again, the alarm
will be reset and the CTLGGIO OPER logic input will be set to the value in the GOOSE message.
A CTLGGIO 61850 logic output and INDGGIO logic input are shown in Figure 14.
Figure 15. CTLGGIO Alarm
IEC61850PTRC Logic Block
The IEC61850PTRC logic block is available to set the corresponding status outputs in the IEC61850
PTRC node. The trip output for the BE1-11 should be connected to the Operate-General input of the
block. If trip statuses of individual phases are known, use BESTlogic
™Plus to connect them to the Phase
A, Phase B, and Phase C logic inputs.
The IEC 61850 PTRC logic block is shown in Figure 16.
BE1-11
BESTCOMSPlus
®