Release of the reflux protection device:
In case the burst protection device interrupted the water supply, find first the reason and remove it as far

as necessary. Close the water tap. Release the valve by a half left-turn of the upper knurled part. You can

hear the release of the valve as a clicking noise. Tighten the burst protection device against the water tap

by a right turn. Open the water tap slowly afterwards.
Maintenance of the assembly of hose burst protection device with reflux protection device:
Calcification can impair the function of both valves. We recommend an annual inspection by a skilled

plumper. The plumper should demount the safety kit with reflux protection device to check both valves by

hand for function and calcification or blockage.

CAUTION

Danger of calcification.
Impairment of valve function.

Have a plumber inspect the two valves annually.

Remove calcifications by citric acid or acetic acid solutions.

Afterwards test the function and the tightness of the mounted unit.

Check: Quickly open the water tap while there is no chamber connected – the valve has to cut off the

water flux without any delay.

4.4 Electrical connection

The constant climate chamber comes with a fixed power connection cable that has a length of 1800 mm /

5.9 ft. The socket must also provide a protective conductor.

Model

Power plug

Voltage

+/-10 %

Current type

Power

frequency

Unit fuse

KBF LQC 240

KBF LQC 720

Shock-proof

plug

200 V to 240 V

1N~

50/60 Hz

16 Amp

Prior to connection and start-up, check the power supply voltage. Compare the values to the specified

data located on the unit’s type plate (left unit side, bottom right-hand, see chap. 1.4).
When connecting, please observe the regulations specified by the local electricity supply company and

as well the VDE directives (for Germany). We recommend the use of a residual current circuit breaker.

Pollution degree (acc. to IEC 61010-1): 2

Installation category (acc. to IEC 61010-1): II

CAUTION

Danger of incorrect power supply voltage.
Damage to the equipment.

Check the power supply voltage before connection and start-up.

Compare the power supply voltage with the data indicated on the type plate.