beautypg.com

7 operation, 1 messages, 2 display elements – Pilz PSSu K F INC User Manual

Page 27: 1 display elements for module diagnostics, Section 7, Operation, Messages, Display elements, Display elements for module diagnostics, 7operation

background image

Operation

Operating Manual PSSu K F INC
1001688­EN­06

27

7

Operation

7.1

Messages

A module error is displayed via the "Err" LED, signalled to the head module and then
entered in the head module's diagnostic log.

The module can detect the following errors:

Module error

Declaration

Remedy

Start­up error

Error as the PSSu system starts
up

Change faulty module.

Configuration error

Incorrect module type configured.

The configured hardware registry
does not match the actual hard­
ware registry.

ST communication error

Error during ST communication

Change faulty module.

Bus termination error

There is no terminating plate or
there is a bad contact with the
module bus.

Install a terminating plate with in­
tegrated end bracket or insert the
base modules together correctly.

7.2

Display elements

Legend:

LED on

LED off

7.2.1

Display elements for module diagnostics

The module has an LED for displaying module errors ("Err" LED).

Err

Err

LED

Meaning

Designation

Colour

Status

Err

­ ­ ­

No error

Red

Module is
faulty