1 safety characteristic data, Safety characteristic data – Pilz PSSu E F ABS SSI User Manual
Page 30

Technical Details
Operating Manual PSSu E F ABS SSI(T)
1001455EN06
30
Mechanical data
312275
314275
Material
Bottom
PC
PC
Front
PC
PC
Coding
PA
PA
Mounting type
plugin
plugin
Dimensions
Height
76,0 mm
76,0 mm
Width
12,6 mm
12,6 mm
Depth
60,2 mm
60,2 mm
Weight
36 g
37 g
Mechanical coding
Type
J
J
Colour
Yellow
Yellow
The standards current on 200504 apply.
8.1
Safety characteristic data
Operating
mode
EN ISO
138491:
2008
PL
EN ISO
138491:
2008
Category
EN IEC
62061
SIL CL
EN IEC
62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
138491:
2008
T
M
[year]
–
PL e
Cat. 4
SIL CL 3
2,61E09
SIL 3
4,43E06
20
If the module is operated at an ambient temperature above 60° C, the values stated in the
table for PFH
D
and PFD will need to be doubled when a safety function is calculated.
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.