Wiring

Operating Manual PSSu E F ABS SSI(­T)
1001455­EN­06

24

Base module

Terminal configuration

Screw terminals:
PSSu BP­C 1/8S
PSSu BP­C 1/8S­T

Cage clamp terminals:
PSSu BP­C 1/8C
PSSu BP­C 1/8C­T

With C­rail:

11: Input D+
(Data +)

21: Output Cl+
(Clock +)

12­22: 0 V counter
(12­22 linked within the base
module)

13­23: C­rail supply,
cable screening
(13­23 linked within the base
module)

14: Input D­
(Data ­)

24: Output Cl­
(Clock ­)

21

11

22

12

23

13

24

14

6.3

Connecting the module

Input and output cir­
cuit

Connecting an SSI en­
coder
(master mode)

With C­rail

Encoder supply via
the PSSu E PD mod­
ule

0 V connection is not
absolutely essential.

21

11

22

12

23

13

24

14

0 V

D+

D-

Cl+

Cl-

0 V

Cl+

D+

Cl-

D-

0 V / GND