Page 14: Integrated protection mechanisms, Configuration, Parameter

Function description
Operating Manual PSSu E F ABS SSI(T)
1001455EN06
14
}
b: The first bit is transmitted with the first rising edge from the Cl signal.
}
c: The time up to the second rising edge is the period length T. 1/T is the signal fre
quency.
}
d: The last rising edge from the Cl signal ends the transfer. The encoder acknowledges
the end of the transfer with a 0 signal.
}
e: The encoder can transfer data again as soon as there is a 1 signal at input D.
4.1.2
Integrated protection mechanisms
When the PSSu E F PS1(T) is used to supply the system, the module supply is buffered
for 20 ms if the supply voltage is interrupted.
The module detects the following errors:
}
Startup error
}
Configuration error
}
ST communication error
}
Bus termination error
4.2
Configuration
4.2.1
Parameter
The module has the following configuration options:
Configuration
Default
value
Meaning
Transmission rate
250 kHz
62.5 kHz
100 kHz
125 kHz
250 kHz
500 kHz
1 MHz
1.5 MHz
Gray code format
On
On: Gray code is activated.
Off: Binary code is activated.
Fault detection within the data
frame
(1)
On
On: Errors within the data frame are identified.
Off: Errors within the data frame are ignored.
Input data length
24
2 ... 32 Bit
(1)
An error within the data frame means that the absolute encoder does not terminate the
serial data transfer with a zero.