Wiring

Operating Manual PSSu E F ABS SSI(­T)
1001455­EN­06

21

6

Wiring

6.1

General wiring guidelines

Please note:

}

Use twisted pair cables to carry the differential signals (D+/D­ and Cl+/Cl­). This will in­
crease the noise immunity.

}

Use shielded signal cables with metallic plugs.

}

On base modules with C­rail:

Connect the shield to the terminals on the C­rail.

Connect the C­rail with low impedance to the functional earth.

}

On base modules without C­rail:

Connect the shield as shown in the terminal configuration section.
The module connects the shield to the mounting rail.

Connect the mounting rail to the functional earth via an earthing terminal.

}

The supply voltages must be extra low voltages with protective electrical separation
(PELV or SELV) in accordance with VDE 0100, Part 410.

}

Use copper wiring.

}

Connect the two sensors via separate cables. This also applies to compact encoders.

}

The terminal configuration as stated on the front plate applies for base modules with C­
rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.

6.1.1

Mechanical connection of the base modules

Procedure:

}

Use a flat blade screwdriver (DIN 5264­A)!

DIN 5264-A

}

Strip the wire back 8 mm.

}

If necessary, label the connection level with a colour marker [3].

}

Base module with screw terminals:

Use a screwdriver to loosen the screw on the screw terminal [1]

Insert the stripped cable into the round fixing hole [2], as far as it will go.

Tighten up the screw on the screw terminal.