7.3

Diagnostic bytes

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-10

7.3.4

Structure and contents of the module byte (Byte 3)

Structure and contents of the module byte (Byte 3)

7-

][BA_Betrieb ST-Bus Modul-Bytes

Diagnostic value Description

0

No diagnostic value available

1

Short circuit

2

Undervoltage error (supply voltage modules)

3

Overvoltage error (supply voltage modules)

4

Overload

5

Temperature error: Too warm

6

Open circuit

7

Input value greater than limit value 2 (limit value monitoring, analogue modules)

8

Input value less than limit value 1 (limit value monitoring, analogue modules)

9

General module error

10

Reserved

11

Reserved

12

Reserved

13

Reserved

14

Reserved

15

Reserved

16

Protocol error

17

Error in the local enable principle (FS output modules)

18

Error in the parameter setup

19

Value below the lower limit value (range monitoring, analogue modules)

20

Value exceeds the upper limit value (range monitoring, analogue modules)

21

Configuration error

22-255

Not defined