beautypg.com

7operation, 1 messages – Pilz PSSu H SB IBSo User Manual

Page 26

background image

7.1

Messages

7

Operation

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-2

(

1

) There are two levels of overtemperature.

Too warm:

If a module's temperature exceeds a threshold value, the module

sends a warning to the head module. If the temperature drops back

below the threshold value, the module sends an all-clear.

Too hot:

If a module's temperature exceeds a further threshold value, the mod-

ule sends an error message to the head module and triggers an

I/O-Group stop.

Further information on PSSu error messages is available in the online

help for the system software.

Overload of the supply voltage for en-
coder

Supply voltage for encoder overload-
ed or short-circuited

Rectify overload or short circuit

Overvoltage error

A system voltage or infeed is too high

Stabilise the supply or change the
faulty supply voltage module

Undervoltage error

A system voltage or infeed is too low

Stabilise the supply or change the
faulty supply voltage module

Error in the overvoltage protection di-
odes

Overvoltage protection diodes are de-
fective

Change faulty supply voltage module

Timeout error on the output

No data has been received for the out-
put from the module bus for longer
than 50 ms.

Check ST communication or configu-
ration

Polarity error

Polarity of the periphery supply

Correct the polarity

Error in the periphery supply

Lower voltage limit exceeded on the
periphery supply

Ensure there is a sufficient supply

Module error

Statement

Remedy