7operation, 1 messages – Pilz PSSu H SB IBSo User Manual
Page 26
![background image](https://www.manualsdir.com/files/762713/content/doc026.png)
7.1
Messages
7
Operation
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
7-2
(
1
) There are two levels of overtemperature.
Too warm:
If a module's temperature exceeds a threshold value, the module
sends a warning to the head module. If the temperature drops back
below the threshold value, the module sends an all-clear.
Too hot:
If a module's temperature exceeds a further threshold value, the mod-
ule sends an error message to the head module and triggers an
I/O-Group stop.
Further information on PSSu error messages is available in the online
help for the system software.
Overload of the supply voltage for en-
coder
Supply voltage for encoder overload-
ed or short-circuited
Rectify overload or short circuit
Overvoltage error
A system voltage or infeed is too high
Stabilise the supply or change the
faulty supply voltage module
Undervoltage error
A system voltage or infeed is too low
Stabilise the supply or change the
faulty supply voltage module
Error in the overvoltage protection di-
odes
Overvoltage protection diodes are de-
fective
Change faulty supply voltage module
Timeout error on the output
No data has been received for the out-
put from the module bus for longer
than 50 ms.
Check ST communication or configu-
ration
Polarity error
Polarity of the periphery supply
Correct the polarity
Error in the periphery supply
Lower voltage limit exceeded on the
periphery supply
Ensure there is a sufficient supply
Module error
Statement
Remedy