beautypg.com

Display elements, Display elements for system diagnostics, 7operation – Pilz PSSu H SB IBSo User Manual

Page 27: 2 display elements, 1 display elements for system diagnostics, Dev usb

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

7-3

7.2

Display elements

7

Operation

7.2

Display elements

7200

Display elements

7-

Anzeige Legende 3x

Legend:

7.2.1

Display elements for system diagnostics

Display elements for system diagnostics

7-

][BA_Anzeige System

The module has LEDs to display various PSSu states (“Usb” LED and

“Dev” LED).

(*

1

) An error on the module bus (flashing red LED) may be due to one of

the following reasons, which are stored in the error stack:

1. The head module cannot determine the registered hardware. Possible

causes:

Module bus is incomplete

Terminating resistor is missing.

A module is defective

A module does not have valid software.

Invalid hardware registry

Too many modules

LED on

LED flashes

LED off

LED

Key

Description

Colour

Status

Usb

- - -

No data is being
transmitted via
the USB port

Green

Data is being
transmitted via
the USB port

Dev

- - -

PSSu system
error, no start-
up

Green

PSSu running
without error

Red

Error in the
head module

Red

Error on the
module bus (*

1

)

Usb Dev

---

---

Dev

Usb