9 technical details, Section 9, Technical details – Pilz PSSu H m F DPsafe SN SD User Manual
Page 34: 9technical details
Technical details
Operating Manual PSSu H m F DPsafe SN SD
1002933EN02
34
9
Technical details
General
312066
Approvals
BG, CE, EAC (Eurasian), TÜV, cULus Listed
Application range
Standard/failsafe
Application in system environment B
From FS firmware version, head modules
1.7.0
System sections
312066
ST resource
No
FS resource
Yes
ST module bus
Yes
FS module bus
Yes
ST SNp interface
Yes
FS SNp interface
Yes
PROFIBUSDP Slave
Yes
IP Connections
IP Connections
Yes
Diagnostic Server
No
OPC Server
No
Programming
312066
IEC 61131 programming
No
Multi programming
Yes
Nonvolatile variables
No
Electrical data
312066
Supply voltage
for
Module supply
Voltage
24 V
Kind
DC
Kind
DC
Voltage tolerance
30 %/+25 %
Max. continuous current that the external power
supply must provide
1,0 A
Output of external power supply (DC)
16,1 W
Supply voltage
for
Periphery supply
Voltage
24 V
Kind
DC
Voltage tolerance
30 %/+25 %
Max. continuous current that the external power
supply must provide
10,0 A
Potential isolation between module supply and peri
phery supply
3050 V
Potential isolation between Module Supply and
PROFIBUS DP
700 V