7 wiring, 1 general wiring guidelines, 2 terminal configuration – Pilz PSSu H m F DPsafe SN SD User Manual
Page 20: Section 7, Wiring, General wiring guidelines, Terminal configuration, 7wiring
Wiring
Operating Manual PSSu H m F DPsafe SN SD
1002933EN02
20
7
Wiring
7.1
General wiring guidelines
Please note:
}
The requirements of the supply voltages can be found in the chapter entitled "Technical
Details".
}
Protective separation must be ensured for the external power supplies that generate
the supply voltages. Failure to do so could result in electric shock.
}
The external power supplies must comply with the current applicable standard EN
609501, EN 61140, EN 50178 or EN 615581.
}
The maximum current load for the periphery supply on the module bus is 10 A. Please
refer to the derating diagram in the chapter entitled "Function Description".
}
Earth the 0 V supply on the periphery supply or monitor each supply group for earth
faults.
}
The connection of the 0 V supply to the central earth bar or earth fault monitor must be
in accordance with relevant national regulations (e.g. EN 602041, NFPA 79:177,
NEC: Article 250).
}
Details of the minimum range for conductor cross sections on connection terminals can
be found in the section entitled "Technical Details".
}
Use copper wiring.
7.2
Terminal configuration
Module supply
Terminal configuration
X1
4pin female con
nector
24V
+24 V infeed for module
supply
24V 24V 0V 0V
X2
24V 0V
X1
0V
0 V infeed for module
supply
Periphery supply
Terminal configuration
X2
4pin female con
nector
24V:
+24 V infeed for peri
phery supply
24V 24V 0V 0V
X2
24V 0V
X1
0V
0 V infeed for periphery
supply
Functional earth