Function description

Operating Manual PSSu H m F DPsafe SN SD
1002933­EN­02

14

INFORMATION

Further information on SafetyNET p can be found in the "PSS 4000 System
Description".

4.7

PROFIBUS­DP with PROFIsafe

4.7.1

Connection to PROFIBUS DP with PROFIsafe

PROFIBUS is an open fieldbus standard whose communication is defined in the interna­
tional standards IEC 61158 and IEC 61784. Further provisions have been defined in spe­
cifications published by the PROFIBUS User Group. These specifications are available
from PROFIBUS International (see www.profibus.com).

The head module has a PROFIBUS­DP interface with PROFIsafe. Communication via
PROFIsafe is defined in the international standard IEC 61784­3­3.

4.7.2

Selector switch for setting the station address

}

The station address of a PSSu is set via the "ADDRESS" DIP switch. The DIP switch is
binary coded. Permitted station addresses are in the range 0

D

 ... 125

D

. If station ad­

dress 126

D

 is set via the DIP switch, the address can be assigned via the Master. The

Set Slave Address command (SSA) must be run for this purpose.

}

The station address of an F­device is set via the "F­ADDRESS" DIP switch. The DIP
switch is binary coded. Permitted station addresses are in the range 1

D

 ... 511

D