7 profibus-dp with profisafe, 1 connection to profibus dp with profisafe, 2 selector switch for setting the station address – Pilz PSSu H m F DPsafe SN SD User Manual
Page 14: Profibusdp with profisafe, Connection to profibus dp with profisafe, Selector switch for setting the station address, 7 profibusdp with profisafe
Function description
Operating Manual PSSu H m F DPsafe SN SD
1002933EN02
14
INFORMATION
Further information on SafetyNET p can be found in the "PSS 4000 System
Description".
4.7
PROFIBUSDP with PROFIsafe
4.7.1
Connection to PROFIBUS DP with PROFIsafe
PROFIBUS is an open fieldbus standard whose communication is defined in the interna
tional standards IEC 61158 and IEC 61784. Further provisions have been defined in spe
cifications published by the PROFIBUS User Group. These specifications are available
from PROFIBUS International (see www.profibus.com).
The head module has a PROFIBUSDP interface with PROFIsafe. Communication via
PROFIsafe is defined in the international standard IEC 6178433.
4.7.2
Selector switch for setting the station address
}
The station address of a PSSu is set via the "ADDRESS" DIP switch. The DIP switch is
binary coded. Permitted station addresses are in the range 0
D
... 125
D
. If station ad
dress 126
D
is set via the DIP switch, the address can be assigned via the Master. The
Set Slave Address command (SSA) must be run for this purpose.
}
The station address of an Fdevice is set via the "FADDRESS" DIP switch. The DIP
switch is binary coded. Permitted station addresses are in the range 1
D
... 511
D