beautypg.com

7 operation, 1 messages, 1 display elements for device diagnostics – Pilz PNOZ m ES CANopen User Manual

Page 19: Section 7, Operation, Messages, Display elements for device diagnostics, 7operation

background image

Operation

Operating Manual PNOZ m ES CANopen
1002699­EN­03

19

7

Operation

7.1

Messages

When the supply voltage is switched on, the PNOZmulti safety system copies the configur­
ation from the chip card.

The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up on the base unit.

The expansion module PNOZ m ES CANopen is configured and started automatically. The
LEDs “RUN” and “ERR” display the status of the PNOZ m ES CANopen on CANopen.

If the expansion module PNOZ m ES CANopen does not receive a configuration from the
base unit for a period of 30 s, the expansion module PNOZ m ES CANopen connects to
CANopen and "RUN" status is displayed on CANopen. The error message "External Error"
is sent to the Master.

7.1.1

Display elements for device diagnostics

LED off

LED flashes

1

LED flashes once

2

LED flashes twice

3

LED flashes three times

LED on

LED

Key

PWR

Supply voltage is present

Supply voltage is not present

RUN

PNOZ m ES CANopen In "Operational" status

1

PNOZ m ES CANopen In "Stopped" status

PNOZ m ES CANopen In "Pre­Operational" status

No supply voltage or module error detected