Commissioning
Operating Manual PNOZ m ES CANopen
1002699EN03
15
6
Commissioning
6.1
Wiring
6.1.1
General wiring guidelines
The wiring is defined in the circuit diagram of the PNOZmulti Configurator.
Note:
}
Information given in the "Technical details" must be followed.
}
Always connect the mounting rail to the protective earth via an earthing terminal. This
will be used to dissipate hazardous voltages in the case of a fault.
}
The power supply must meet the regulations for extra low voltages with protective sep
aration.
CAUTION!
Only connect and disconnect the expansion module when the supply
voltage is switched off.
NOTICE
When installing, you must refer to the guidelines of theCANopen user
group.
6.1.2
Connecting the supply voltage
Connect the supply voltage to the fieldbus module:
}
Terminal 24 V: + 24 V DC
}
Terminal 0 V: 0 V
6.1.3
CANopen interface
The connection to CANopen is made via a male 9pin DSub connector.
5
1
6
9
1: n.c.
2: CAN_L
3: CAN_GND
4: n.c.
5: CAN_SHLD
6: n.c.
7: CAN_H
8: n.c.
9: n.c.
n.c. = not connected
Please note the following when connecting to CANopen: