Commissioning

Operating Manual PNOZ m ES CANopen
1002699­EN­03

16

}

Only use metal plugs or metallised plastic plugs

}

Twisted pair, screened cable must be used to connect the interfaces

6.1.3.1

CANopen termination

To minimise cable reflection and to guarantee a defined rest signal on the transmission line,
CANopen must be terminated at both ends.

6.2

Preparing for operation

6.2.1

Setting the transmission rate

1

23

4

9

8

7

6

0

5

DR

}

On the upper rotary switch DR, use a small screwdriver to set the transmission rate (in
the example, "3" corresponds to 50 kBit/s).

Switch setting

0

1

2

3

4

5

6

7

8

9

Transmission rate

­

10

kBit/s

20

kBit/s

50

kBit/s

125

kBit/s

250

kBit/s

500

kBit/s

800

kBit/s

1

MBit/s

­

INFORMATION

The transmission rate cannot be changed during operation.

6.2.2

Setting the station address

The station address of the expansion module PNOZ m ES CANopen is set between 0 ... 99
(decimal) via two rotary switches x1 and x10.