NOTE:
This device uses an adaptive
Gain and Phase adjustment mechanism
and should not be changed
•
Changes to these attribute through
the DeviceNet port is volatile
(non recorded in NVRAM)
•
Control optimization is done in
real time and there is no learning
calibration sequence
9.10 - S-Analog Actuator Object
Class ID 32
hex
Instance ID 1
9.11 - S-Single Stage Controller Object
Class ID 33
hex
Instance ID 1 (process control)
Instance ID 2 (position control)
NOTE:
There is no subclass
for instance 2
TAbLE 9.10.1 – S-ANALOG ACTUATOR ObJECT ATTRIbUTES
AttrIBute ID
hex
AcceSS coDe
nAme
FormAt
vAlue
5
10 (set)
Override
UINT
Override for the valve
0 = closed; 7FFFh=open
6
0E (get)
Value
INT
Analog output value
7
0E (get)
Status
BYTE
Alarm & Warning, Default = 0
TAbLE 9.10.2 –S-ANALOG
ACTUATOR EXCEPTION
STATUS bITmAP
BIt
DeFInItIon
0
High Alarm
1
NA
2
High Warning
3
NA
4-7
reserved
TAbLE 9.11.2 – S-SINGLE STAGE CONTROLLER ObJECT SUbCLASS ATTRIbUTES
AttrIBute ID
hex
AcceSS coDe
nAme
FormAt
vAlue
06
10 (set)
Setpoint
UINT
0 to 7FFFh for close to open
0A
0E (get)
Status
BYTE
Alarm & Warning, Default = 0
TAbLE 9.11.1 – S-SINGLE STAGE CONTROLLER ObJECT ATTRIbUTES
AttrIBute ID
hex
AcceSS coDe
nAme FormAt
vAlue
06
10 (set)
Setpoint
UINT
0 to 7FFFh
for 0 to 100%
0A
0E (get)
Status
BYTE
Alarm & Warning,
Default = 0
63
0E (get)
Subclass
UINT
1 for PID and source select
5C
0E (get) 10 (set)
phase
UINT
Control Phase
5E
0E (get) 10 (set)
Gain
UINT
Proportional Gain
60
0E (get) 10 (set)
Process
variable
source
BYTE
0 network
1 if acquisition is from CDG1
2 if acquisition is from CDG2
3 automatic
PID and source select subclass 01 is used.