18.3.3
Maximum rate check and adjustment
i
To verify the maximum gas rate CO
2
setting the
appliance must be checked at the maximum rate.
• Activate the test mode "P.01" and set the value to 100 in order
to force the burner at P. max. See chapter "Specific adjustment
▸ Appliance technical settings and parameter list ▸ Test
modes".
• Wait approximately 5 minutes to read a stabilised CO
2
value.
• Check that the value is within the range specified in table in
the “check” column.
G20 burner % CO
2
Model
Check (case on)
Setting (case off)
CO/CO
2
ratio
35 Store
9.2 ± 0.3%
9 ± 0.2%
0.004
G31 burner % CO
2
Model
Check (case on)
Setting (case off)
CO/CO
2
ratio
35 Store
10.3 ± 0.3%
10.1 ± 0.2%
0.004
If the combustion reading is not within the acceptable values
and the integrity of the complete flue system and combustion
circuit seals have been verified and the inlet gas pressure (and
gas rate) have been verified, then, it will necessary to adjust the
combustion rate of the appliance.
i
Adjustment is made by turning the throttle an ⅛
of a turn, waiting 1 minute to allow the appliance
to stabilise before checking or making further
adjustments.
• Remove the sticker covering the “throttle” adjustment screw,
if fitted.
• Rotate the “throttle” (1) (anti-clockwise to increase), to the
required CO
2
, refer to previous diagram and the “Setting”
column in the table.
• When you have finished, press the On/Off button to exit the
test modes.
• Remove the analyser probe and replace the cap on the
sampling point, replace the controls fascia, and the front
casing panel.
i
Remember to replace the sample point cap on
completion of the test.
18.3.4
Gas rate check
• Check the gas rates as described in the commissioning
section.
18.3.5
Completion
If it is not possible to achieve the required results for either the
combustion or gas rates, it will be necessary to complete a full
service of the appliance and then repeat the combustion check
procedure.
If after servicing and adjustment of the appliance the combustion
values are still unacceptable and after further remedial work has
been carried out, the appliance must be disconnected until the
CO/CO
2
ratio is acceptable.
• Advice can be sought from the Glow-worm Technical Helpline.
18.4 Servicing
i
If the Combustion CO
2
, CO/CO
2
ratio & Gas rate
checks did not require adjustment then it will not be
necessary to complete a full service.
All routine servicing requirements can be achieved by the removal
of the front panel.
• Position the control box into the service position.
• Before commencing with a service or replacement of parts,
isolate the boiler from the electrical and gas supplies.