Installation – Glow-worm Ultracom2 35 Store User Manual
Page 34

0020112185_PROTO_13 - 01/11 - Glow-worm
- 32 -
Code Parameter
Unit
Description
factory
setting
Modifiable
parameter
d.00 Maximum heating power
kW
Choose a value:
8 to 30 kW
30
yes
d.01 Pump over-run time - heating
min. Choose a value between 2 and 60.
5
yes
d.02 Blocking time for burner in heating
mode (anti-cycle time)
min.
To prevent the burner frequently switching on and off,
the reactivation of the burner is electronically blocked for a period
that is determined each time the burner stops. The burner blocking
time can be adapted to the usage conditions for the heating
installation and depends on the temperature that is set for heating:
- at 80°C, the period is fixed (2 minutes)
- at 10°C, the period is adjustable: choose a value between 2 and 60
minutes.
20
yes
d.03 Plate exchanger inlet temperature.
°C
Display of the plate exchanger inlet temperature on the short circuit
-
no
d.04 Temperature of water in the tank
°C
Display tank water temperature.
-
no
yes
Pump function
-
Mode:
0 = With the burner
1 = Continuous with ambient temperature
2 = Continuous
1
yes
yes
Speed of the pump
-
Functioning mode:
0 = Automatic: maximum speed when the burner is switched on
1 = Minimum speed
2 = Automatic: automatic speed when the burner is switched on
3 = Maximum speed
2
yes
yes
Maximum temperature setting for
domestic hot water
°C
The recommended maximum temperature setting for domestic hot
water is 60°C. Choose a value suitable for your needs.
60
yes
The following 2 menus are displayed if an option card (not supplied) is installed on the appliance.
d.27 Function relay 1
-
Attributing a function to relay 1 of the option card:
1 = Domestic hot water circulation pump
2 = auxiliary heating pump
3 = Reservoir loading pump
4 = smoke valve / chimney extractor
5 = external gas valve
6 = external error message
1
yes
d.28 Function relay 2
-
Attributing a function to relay 2 of the option card:
1 = Domestic hot water circulation pump
2 = auxiliary heating pump
3 = Reservoir loading pump
4 = smoke valve / chimney extractor
5 = external gas valve
6 = external error message
2
yes
The following menu displays automatically if an automatic fill kit is installed on the appliance.
d.31 Refill method
-
Operating mode:
0 = Manual
1 = Semi-automatic
2 = Automatic
0 or 2
-
d.34 Speed of fan
tr/
min.
Fan speed is displayed between 0 and 99.
Multiply the displayed value by 100.
-
no
d.35 Position of 3-way valve
-
0 = Heating
100 = Hot water
-
no
d.36 Domestic hot water flow
l/
min. Display domestic hot water flow.
-
no
The following menu is displayed if a solar system (not supplied) is connected to the appliance
d.39 Solar circuit water temperature
°C
Displays the water temperature measured by the sensor located
upstream of the mixer.
-
no
d.40 Heating flow temperature
°C
Display the heating flow temperature.
-
no
d.41 Heating return temperature
°C
Display the heating return temperature.
-
no
INSTALLATION