beautypg.com

Fig. 3 — unit leveling tolerances, Outdoor-air inlet adjustments, Condensate drain – Carrier 50LJ User Manual

Page 8

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

NOTE: To prevent the hazard of stagnant water build-up in the drain

pan of the evaporator section, unit can only be pitched as shown.

See Table 1 for allowable B tolerances.

DIMENSIONS (degrees and In.)

UNIT

B

C

D

Deg

In.*

Deg

In.*

Deg

In.*

48U

1 38

4.00

50LJ

1.00

3.25

.50

.75

.50

.75

50LW

1.38

4.00

'From edge of unit to horizontal

Fig. 3 — Unit Leveling Tolerances

Condensate Drain

— See Fig. 5a - 5c for drain

location. A drain assembly consisting of a 10-gage plate

with PA in. half coupling welded to it is shipped inside the
base unit, taped to the basepan in the filter section. Open
the access panel marked FILTER SECTION and fine drain
assembly and the 4 screws required to mount it in the left-
hand comer. After unit has been set in place on the roof,
remove drain assembly and attach it to the bottom of the
unit base rail using the screws provided. See Fig. 4. Use a
trap at least 4-in. deep and protect against freeze-up.

On slab mount applications, and when mounted on

sleepers, seal hole in bottom of base rail and attach drain
assembly as low as possible to side of base rail.

NOTE: Drain hole must be drilled in rail. There is no factory-

supplied drain hole in the side of the base rail.

Outdoor-Air Inlet Adjustments

ECONOMIZER SETTINGS
Enthalpy Sensor (Fig. 61 — This sensor is located on the
partition separating the outdoor air from the return air. See
Fig. 7. The enthalpy setting adjustment is on the top of the
economizer motor. See Fig. 8. For maximum benefit of out­
door air, set enthalpy control to the A setting. See Fig. 8
and 9.
Mixed-Air Thermistor — The mixed-air thermistor (MAT)
set point adjustment is on the top of the economizer motor.
This motor is located in the retum-air section, and is

accessed by opening the access panel marked FILTER
SECTION. See Fig. 8. Set MAT set point adjustment dial
to the desired setting. The factory setting is 55 F ± 5° F;
the range is 40 to 90 F. The MAT is located on the filter
rack.
Minimum Damper Position Set Point — The minimum po­
sition adjustment is located on the cover of the economizer
motor. See Fig. 8. Adjust by setting the fan switch to ON
position (continuous fan operation), and setting the system
selector switch to OFF position. Then turn adjustment screw
slowly until the dampers assume the desired vent position.
Do not manually operate the damper motor, damage to the
motor my result.

BOTTOM OF
BASE RAIL

Fig. 4 — Condensate Drain Piping Details