beautypg.com

Protective devices – Carrier 50LJ User Manual

Page 29

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

ENTHALPY CONTROL, MAT, AND ECONOMIZER
DAMPER VENT POSITION — See Installation section of
this publication for adjustment procedures.

AUXILIARY SWITCH — All units have an auxiliary switch
located on the economizer damper motor. This switch is
factory set to prevent the power exhaust from operating when
the economizer damper is less than 50% open. If other than

the factory setting is desired, follow the steps below.

A

CAUTION

Do not turn motor shaft by hand or with a wrench.
Damage to the gear train will result.

TO ADJUST CAMS,

MOVE TOP OF SCREWDRIVER ONLY

2

.

Remove top cover from motor to gain access to motor
terminals and cam adjustments.
Disconnect controller from motor. Connect red, white,

and blue terminals on the 135 ohm manual potentiome­
ter to corresponding red, white and blue terminals on
the motor. Connect 24-vac power to Terminals 1 and 2.
See Fig. 28.

3. Adjust the 135-ohm potentiometer so that the motor shaft

turns to the position where auxiliary equipment is to be
switched.

4. Adjust auxiliary cam by inserting a Vs-in. straight blade

screwdriver into slot on cam and moving TOP of screw­
driver to the right or left. See Fig. 29.

5. To close auxiliary switch red and blue contacts as the

motor travels open (energizing the power exhaust mo­
tor), the switch differential can only be 10 degrees on
both switches. To adjust either cam, perform the fol­
lowing steps:

a. If red and blue contacts are open, rotate the cam

counterclockwise until the contacts close.

b. If the red and blue contacts are closed, rotate the cam

clockwise until the contacts open.

6. Check for proper auxiliary switching (including differ­

ential) by mnning motor through full stroke, using 135
ohm potentiometer. Repeat adjustment if necessary.

7. Disconnect 135 ohm potentiometer, reconnect control­

ler and place top cover on motor.

AUXILIARY END VIEW

Fig. 28 — Auxiliary Switch Stroke Adjustment

Fig. 29 — Auxiliary Switch Adjustment

NOTE: Adjusting the auxiliary switch does not require run­
ning the motor.

REFRIGERANT CHARGE — All units are shipped with a
complete operating charge of R-22. See unit nameplate and
Tables la and lb for amount of charge. When charging
refrigerant system, refer to Carrier Standard Service Tech­
niques, Refrigerants section. When adding a complete charge,
evacuate system using standard evacuating procedures and

weigh in the specified amount of charge. See Fig. 30 for
refrigerant circuit charging chart.

Refrigerant Feed Components

— Each refrigerant

circuit (2 per unit) has all the necessary refrigerant
controls.

Acutrol™ Refrigerant Metering Device

- Each

circuit has 12 non-adjustable metering devices. They con­
trol the flow of liquid refrigerant to the evaporator coils.

Filter Drier

— Replace whenever refrigerant system is

exposed to atmosphere.

Protective Devices

COMPRESSOR PROTECTION
Overcurrent (208/230 v onlvl — Each compressor has one
manual reset, calibrated trip, magnetic circuit breaker. Do
not bypass connections or increase the size of the circuit
breaker to correct trouble. Determine the cause and correct

it before resetting the breaker.

29