beautypg.com

Fig. 30 — charging chart, Gas heat, Relief devices – Carrier 50LJ User Manual

Page 30: Control circuit, 115-v, Control circuit, 24-v

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

689

621

3^52

o

in

¡483

UJ

cc

S 41 4

in

cc

Q.

2 345

z

o

5276

:

d

in

207

1 1 1 M 1 1

OUTDOOR TEMP

F C

115 46

105 41

95 35

85 29

75 24

65 18

55 13

45 7

?"

ina.

2=

y' >

'

a:

13

in

in

1

>

" 1

X'

>

«

?

z

_J

y

orj

in

3

5

0

4

JCTION L

0

5

NE TEMPE

0

6

RATURE C

0

7

F)

0 8

0

1 1 1 1 1 1 1

-1 4 10 16 21 27

SUCTION LINE TEMPERATURE (C)

Table 6 - Pressure Switch Settings (psig)

Fig. 30 — Charging Chart

SWITCH

CUTOUT

CUT-IN

High

426 ± 7

320 ± 20

Low

7 ± 3

22 ± 5

Overtemperature — Each compressor has an internal pro­
tector to protect it against excessively high discharge gas
temperatures.

r.rankcase Heater — Each compressor has a 70-watt crank­

case heater to prevent absorption of liquid refrigerant by oil
in the crankcase when the compressor is idle. Since 115-v
power for the crankcase heaters is drawn from the unit con­
trol circuit, main unit power must be on for the heaters to
be energized.

IMPORTANT: After a prolonged shutdown or ser­
vice job, energize the crankcase heaters for 24 hours
before starting the compressors.

Compressor Lockout — If any of the safeties (high-, low-
pressure, compressor internal thermostat) trip, or if there is
loss of power to the compressors, the constant volume con­

trol board will lock the compressors off. To reset, manually
move the thermostat setting.

EVAPORATOR FAN MOTOR PROTECTION - A man­
ual reset, calibrated trip, magnetic circuit breaker protects
against overcurrent. Do not bypass connections or increase
the size of the breaker to correct trouble. Determine the
cause and correct it before resetting the breaker.

CONDENSER-FAN MOTOR PROTECTION - Each
condenser-fan motor is internally protected against over­
temperature. Each motor is also protected against a severe
overcurrent condition by manual reset, calibrated trip, mag­
netic circuit breakers. As with the circuit breakers
described previously, do not bypass connections or in­
crease breaker size to correct trouble. Determine the cause

and correct it before resetting the breaker.

HIGH- AND LOW-PRESSURE SWITCHES - See Fig. 31
for compressor mounting locations. Settings for these switches

are shown in Table 6. If either switch trips, or if the
compressor overtemperature switch activates, that refriger­
ant circuit will be automatically locked out by the constant
volume control board. To reset, manually move the ther­
mostat setting.

Relief Devices

— All units have relief devices to pro­

tect against damage from excessive pressures (i.e., fire).
These devices protect the high and low side.

Control Circuit, 115-V

- This control circuit is pro­

tected against overcurrent by a 5-amp circuit breaker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.

Control Circuit, 24-V

— This control circuit is pro­

tected against overcurrent by a 3.2-amp circuit breaker. Breaker
can be reset. If it trips, determine cause of trouble before
resetting.

Gas Heat

LIMITS SWITCHES — The maximum supply air temper­
ature is controlled by a limit switch located in the compres­
sor section. The limit is designed to trip at 100° F above the
maximum temperature shown in Table 1.

When the limit trips, the gas valve is deenergized and the

combustion air blower(s) and evaporator fan are held on
until the unit is cooled to its reset temperature. Once the
unit cools, the gas valve is reenergized.

If the thermostat stops calling for heat after the limit switch

trips, the combustion-air blower and evaporator fan are held
on until the limit cools to its reset temperature.
ROLLOUT SWITCH — This switch senses any flame or
excessive heat in the main burners and deenergizes the gas
valve. If this occurs, the gas heating system is locked out
until the rollout switch is reset manually. Reset by pressing
the button on the rollout switch. See Fig. 21 and 22.

When the rollout switch trips, it likely indicates a flue

blockage. Inspect the unit for any obstruction in the flue

system, for holes on the flue box, or for a defective
centrifugal switch or a loose combustion blower. See
Fig. 32 for proper location of the rollout capillary.

AIRFLOW SWITCH, 48LJE (HIGH HEAT) UNITS ONLY

— Shuts off the gas heat in the event there is a loss of air

over the gas cells. The airflow switch is located in the fan
section (see Fig. 5a — 5c). The switch will automatically
reset when airflow is sufficient.

30