1 Rig with 4 cables and spread with two 95-in. (2413-mm) and
2 “A” long suitable spreader bars.
2 Center of gravity and unit weight include economizer, but not econ
omizer hood
NOTES:
A CAUTION
1 All panels must be in place when rigging.
2. Unit is not designed for handling by forklift truck.
3/4 IN (19 MM) NOTCHES
IN END OF SPREADERS
NOTICE TO RIGGERS
MODEL
UNIT WEIGHT
A
B
C
Lb
Kg
In.
mm
In.
mm
In.
mm
48LJD
2895
1313
85 91
2182
61
1549
43
1092
49LJE
2975
1349
85.91
2182
61
1549
43
1092
50LJ
2565
1164
6.14
1680
49
1245
44
1118
50LW
2775
1259
85.91
2182
61
1549
43
1092
ACCESSORY/OPTION WEIGHTS
ROOF CURB
ECONOMIZER
WITHOUT HOOD
ECONOMIZER
HOOD
POWER EXHAUST/
BAROMETRIC
RELIEF HOOD
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
280
127
140
63.6
155
70.3
130
59.1
Fig. 1 — Rigging Labei
Field-Fabricated Ductwork
— Secure all ducts to
building structure, using flexible duct connectors between
roofcurb and ducts as required. Ducts passing through an
unconditioned space must be insulated and covered with a
vapor barrier. Outlet grilles must not lie directly below unit
discharge.
48LJ UNITS — These units are field-convertible with the
use of an accessory horizontal conversion kit. They are shipped
from the factory as vertical supply/retum, but may be field
converted to horizontal supply/retum.
Attach field-fabricated ductwork to the roof curb. The
retum-air duct connection (inside dimensions) is 46.75-in.
long X 30.59-in. wide; the supply-air duct connection (in
side dimensions) is 38.63-in. long x 27-in. wide. Connect
ductwork to 16-gage roof curb material. Secure all ducts to
the building structure, using flexible duct connectors be
tween roof curb and ducts as required. Ducts passing through
an unconditioned space must be insulated and covered with
a vapor barrier. Outlet grilles must not lie directly below
unit discharge. The return duct must have a 90-degree el
bow before opening into the occupied building space if unit
is equipped with power exhaust.
Vertical discharge ducts are designed to be attached to
accessory roof curb. If unit is mounted on dunnage, it is
recommended that the ducts be supported by cross braces
as shown for accessory roof curb. Duct should be the same
size as shown on the roof curb certified drawing.
Units may be connected to horizontal supply/retum
ductwork with the use of the accessory horizontal conver
sion package.
50LJ UNITS — On these units, attach field-fabricated
ductwork to roof curb. The retum-air duct connection
(inside dimensions) is 49.81-in. long x 30.59-in. wide; the
supply-air duct connection (inside dimensions) is 37.87-in.
long X 31.02-in. wide. Connect ductwork to 16-gage roof
curb material. (See installation instractions shipped with
accessory roof curb.)
50LW UNITS — On these units, attach field-fabricated
ductwork to factory-supplied duct flanges mounted on the
side of the unit. See Fig. 5c. Duct flange height is approx
imately one inch; flange is 18-gage sheet metal. The hori
zontal supply and return duct openings (inside dimensions)
are 26.85-in. wide x 42.03-in. high.