beautypg.com

Carrier 50LJ User Manual

Page 33

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

8

. To verify compressor lockout logic:

a. Disconnect CLO sensor wires connected to CLOl at

the control board. Check wires for continuity. If there
is no continuity, replace the sensor.

b. Connect the multimeter to read voltage between Pin

X at plug PI and ground.

c. Turn unit power on and check the multimeter. Within

a few seconds the meter should indicate 24 v. If it
does not, the control board is defective and must be
replaced.

d. Turn unit power off. Use a toggle switch to connect

a fresh 1.5-v battery to the terminals marked CLOl
as shown in Fig. 34.

A

CAUTION

The negative (- Ve) pole of the battery must be
connected to the inner terminal and the positive

(+ Ve) pole must be connected to the outer ter­
minal as shown in Fig. 34.

e. Turn unit power on and use the toggle switch to make

and break the connection between the outer CLOl
terminal and the positive (-h Ve) pole of the battery.

If the multimeter shows 24 v when battery is dis­
connected and no voltage when the battery is con­
nected, the CLO logic is good. If the multimeter shows
no change, the CLO logic is defective and the board
must be replaced.

1. Be sure unit power is OFF. Disconnect the 2 wires at­

tached to the terminals marked SC2.

2. Check continuity between the 2 wires. If there is no con­

tinuity, the problem is external to the control board
(possibly the pressure switches). If there is continuity,
proceed to Step 3.

3. Reconnect the wires removed in Step 1 above.
4. Turn unit power off. Disconnect plug PI from the con­

trol board and install jumper wire across Pins R and Y2
at plug PI. (This may have already been done in the
Compressor no. 1 troubleshooting section.)

5. Connect a voltmeter across the coil for Compressor no.

2

contactor.

6

. Energize unit and monitor the voltage for a few

seconds.

Sym ptom : Com pressor No. 2 W ill Not Operate.

IMPORTANT: Do not run compressor too long.

7. a.

b.

If proper voltage is indicated at the contactor, but
contactor fails to close, replace contactor.

If voltage is indicated for a few seconds (i.e., the
contactor momentarily pulls in and is then de­
energized), the Compressor Lockout (CLO) logic has
shut down the unit. This is an indication that the board
is not sensing proper compressor current, or that one
of the safeties has tripped. Proceed to Step 8 to ver­
ify compressor lockout logic operation.

If proper voltage is indicated at the contactor and con­
tactor closes, the board is operating properly.

PI

33