beautypg.com

Field electrical connections – Carrier 50LJ User Manual

Page 15

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

terminals on terminal blocks. See control wiring section on
page 17.
ROUTING THROUGH SIDE OF UNIT - When 200-amp
or smaller disconnect is used, route power wiring in
field-supplied watertight conduit into unit through 3Vs in.
knockout. Strain relief (field supplied) must be used in knock­
out. When 400-amp disconnect is used, remove 7% in. x
20-in. block-off in comer post and use field-supplied elbow
to route conduit through comer post to the control box.

Use field-supplied strain relief going into control box through

4

V

2

in. diam hole provided. After wires are in unit control

box, connect to power terminal block. See power wiring

section below.

Bring low-voltage control wiring through field-drilled Vs-in.

diameter hole in condenser side post. Use strain relief go­
ing into one-in. diameter hole in upper righthand comer of
unit control box.

After wiring is in control box, make connection to proper

terminals on terminal blocks. See control wiring section on
page 17.

Field Electrical Connections

POWER WIRING (All units) — Units are factory wired
for the voltage shown on the unit nameplate. The main ter­
minal block is suitable for use with aluminum or copper
wires.

When installing units, provide a disconnect per NEC

(National Electrical Code) of adequate size (MOCP [max­

imum overcurrent protection] of unit is on the informative
plate). All field wiring must comply with NEC and all local
codes. Size wire based on MCA (minimum circuit amps)
on the unit informative plate. See Fig. 13 for power wiring
connections to the unit power, terminal block and equip­
ment ground.

Operating voltage to the compressor must be within the

voltage range indicated on the unit nameplate. Voltages be­
tween phases must be balanced within 2%, and the current
must be balanced within 10%. See Tables 2 and 3 for unit
electrical data.

= 100

X

Use the following formula to determine the percent volt­

age imbalance.
% Voltage Imbalance

max voltage deviation from average voltage

average voltage

Example: Supply voltage is 460-3-60

AB =452

V

BC =464

V

AC =455

V

452 +462 -1-455

Average Voltage

1371

3

= 457

Determine maximum deviation from average voltage:

(AB) 457 - 452 =5 v
(BC) 464 - 457 =7

V

(AC) 457 - 455 =2 v

Maximum deviation is 7 v.

Determine pereent voltage imbalance:

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is be­
low the maximum allowable 2%.

IMPORTANT: If the supply voltage phase im­
balance is more than 2%, contact local utility
immediately.

Unit failure as a result of operation on improper line

voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such opera­
tion would invalidate any applicable Carrier warranty.

Table 2 — Electrical Data, 48LJ024

NOMINAL

V-PH-HZ

VOLTAGE

RANGE

COMPR

NO. 1

COMPR

NO. 2

OFM

IFM

POWER

EXHAUST

FAN MOTOR

POWER SUPPLY

Min

Max

RLA

LRA

RLA

LRA

Total

FLA

Hp

FLA

FLA

MCA

MOCP

Fuse Only

208/230-3-60

187

254

38.5

193.0

38 5

193.0

10.8

50

15.2

6.6/6.0

101 8/112.6
108.4/118 6

150/150
150/150

7.5

22.0

6.6/6.0

108.6/119.4
115.2/125.4

150/150
150/150

460-3-60

414

508

193

96.5

193

96.5

5.4

50

7.2

30.0

56.0
59 0

70
70

7.5

10.5

3.0

59.3
62.3

70
80

575-3-60

518

632

144

77.2

144

77.2

48

50

5.2

2.4

42.4
44 8

50
50

7.5

86

2.4

45.8
48.2

60
60

FLA —

Full Load Amps

Hp —

Nominal Horsepower

IFM —

Indoor (Evaporator) Fan Motor

LRA —

Locked Rotor Amps

LEGEND

MCA

Minimum Circuit Amps (for wire sizing)

MOCP —

Maximum Overcurrent Protection

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

15