9 | VZ7260B Series - Installation Guide

Pressure dependent VAV cooling or heating system with local On-Off

perimeter reheat and central changeover

Mandatory

RehtConf = 3 =
On-Off Perimeter
Reheat Only

Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays

Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control

Mandatory

RehtConf = 3 =
On-Off Perimeter
Reheat Only

Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays

Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control

Pressure dependent VAV cooling or heating system with local On-Off duct

reheat and central changeover

Mandatory

RehtConf = 2 =
On-Off Duct
Reheat Only

Set BO5 Time to
0= 15 minutes if
using regular 24
VAC relays

Set BO5 Time to
1= 10 seconds if
using 24 VAC
Solid State Relays
(SSRs) for
proportional control

Tri-State Floating VAV Actuator

Heating and/or Cooling

& On/Off Baseboard

Room Temperature Control

Minimum & Maximum Position
Adjusted at Controller

UI3

0 V~ Com

24 V~ Hot

BO1

BO5-Aux

BO5-Aux

BO2

R

Close

Open

Analog VAV Actuator

Heating and/or Cooling

& On/Off Baseboard

Room Temperature Control

Minimum & Maximum Position
Adjusted at Controller

0 to 10

VDC

UI3

0 V~ Com

24 V~ Hot

AO1

BO5-Aux

BO5-Aux

AO2

R

Analog VAV Actuator

Heating and/or Cooling

& On/Off Duct Heater

Room Temperature Control

Min, Max and HeatFlow
Positions Adjusted at Controller

1

C

0 to 10

VDC

UI3

0 V~ Com

24 V~ Hot

AO1

BO5-Aux

BO5-Aux

AO2