20 | VZ7260B Series - Installation Guide

5 = Duct heater & On-Off/Pulsed perimeter reheat (All
electric)

Zone will operate in VAV heating or cooling based on the
Master RTU mode and use 2 stages of local reheat.

The first reheat stage will use the modulating BO5 reheat
output (10s or 15m cycles) for a local modulating electric
duct reheat device with a 24 Vac fired SSR. The local reheat
stage can be enabled or disabled based on the outdoor air
temperature and BO5 OALK

The second reheat stage will use the reheat output BO3
(15m cycles) and/or BO4 (10s cycles) for a local On-
Off/Pulsed perimeter reheat device like a 2 position electric
baseboard unit. The local reheat stage can be enabled or
disabled based on the outdoor air temperature and FO2
OALK