26 | VZ7260B Series - Installation Guide

CL Perfo

Controller’s cooling
performance

Default value: None

Not a configuration parameter. Only displays the
controller’s performance in cooling mode.

This value is only valid if there’s no change in system

mode, setpoints or occupancy for at least 1.5 hours. These

changes cause the value to reset to an invalid value

(above 20°F)

UI3 Dis

UI3 display value

Used as diagnostic or service help to troubleshoot and

diagnose sensor operation

Supply or Discharge temperature

CO2

Room CO2 value

Used as diagnostic or service help to troubleshoot and

diagnose sensor operation. This value is displayed only if

AI4 parameter is set to CO2.

0 to 2000 ppm

AI4

I

NPUT FOR

CO2

S

ENSOR

The VZ7260x5x00B series features a 0-10VDC CO2 sensor input which value can be used
by the VZ7656E1000B controller for Indoor Air Quality (AIQ) control.

Here’s the table showing the CO2 value treatment based on the AI4 parameter settings:

AI4

parameter

setting

CO2 display

at the

controller

Value Written to

VZ7656E1000B

Room CO2

Value available

in ppm (BACnet

object)

AI4 Value

available in

VDC (BACnet

object)

None

NO

NO

NO

YES

CO2

YES

YES (Only in

Occupied mode)

YES

YES