31 | VZ7260B Series - Installation Guide

RehtConf = 3 = On-Off Perimeter Reheat Only

VZ7260F Series: Analog Outputs

VZ7260C Series: Floating Outputs

Temperature increase

AO1

Device

On

Device

Off

BO5

CC6

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode
RehtConf = 2 (On/Off Duct Reht Only)
AO2 = Off

Device opened

10 Vdc or Max Pos

Device closed

Min Pos

if DisMinPo = Enabled

or

0 Vdc

if DisMinPo = Disabled

Temperature increase

Device closed

Min Pos

AO1

Cooling

Setpoint

RTC in cooling mode
RehtConf = 3 ( On/Off Peri Rht Only)
AO2 = 0%

CC7

DEAD BAND

Heating

Setpoint

Device Off

Device On

BO5

AO1

Device opened

10 Vdc or Max Pos

AO1 = 0Vdc

if DisMinPo = Disabled

Temperature increase

BO1-BO2

Device

On

Device

Off

BO5

CC6

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode
RehtConf = 2 (On/Off Duct Reht Only)
BO3-BO4 = Off

Device opened

100% or Max Pos

Device closed

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled

Temperature increase

Device closed

Min Pos

BO1-BO2

Cooling

Setpoint

RTC in cooling mode
RehtConf = 3 ( On/Off Peri Rht Only)
BO3-BO4 = 0%

CC7

DEAD BAND

Heating

Setpoint

Device Off

Device On

BO5

BO1

-

BO2

Device opened

100% or Max Pos

BO1-BO2 = 0%

if DisMinPo = Disabled