Referenced operational control curves, Eferenced, Perational – Viconics VZ7260X Installation Guide User Manual

Page 27: Ontrol, Urves

background image

27 | VZ7260B Series - Installation Guide

R

EFERENCED

O

PERATIONAL

C

ONTROL

C

URVES

RehtConf = 0 = None

VZ7260F Series: Analog Outputs

VZ7260C Series: Floating Outputs

Temperature increase

Device opened

10 Vdc or Max Pos

AO1

RTC in Heating mode
RehtConf = 0 (No reheat at the zone

CC2

Device closed

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

AO2 = 0 Vdc & BO5 = Off

Min Pos

if DisMinPo = Enabled

or

0 Vdc

if DisMinPo = Disabled

Temperature increase

Device opened

10 Vdc or Max Pos

Device closed

Min Pos

if DisMinPo = Enabled

AO1

Cooling

Setpoint

RTC in Cooling mode
RehtConf = 0 (No reheat at the zone)

CC1

DEAD BAND

Heating

Setpoint

AO2 = 0 Vdc & BO5 = Off

or

0 Vdc

if DisMinPo = Disabled

Temperature increase

Device opened

100% or Max Pos

Device closed

Min Pos

if DisMinPo = Enabled

BO1-BO2

Cooling

Setpoint

RTC in Cooling mode
RehtConf = 0 (No reheat at the zone)

CC1

DEAD BAND

Heating

Setpoint

BO3-BO4 = 0% & BO5 = Off

or

0%

if DisMinPo = Disabled

Temperature increase

Device opened

100% or Max Pos

BO1-BO2

RTC in Heating mode
RehtConf = 0 (No reheat at the zone)

CC2

Device closed

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

BO3-BO4 = 0% & BO5 = Off

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled