Referenced operational control curves, Eferenced, Perational – Viconics VZ7260X Installation Guide User Manual
Page 27: Ontrol, Urves

27 | VZ7260B Series - Installation Guide
R
EFERENCED
O
PERATIONAL
C
ONTROL
C
URVES
RehtConf = 0 = None
VZ7260F Series: Analog Outputs
VZ7260C Series: Floating Outputs
Temperature increase
Device opened
10 Vdc or Max Pos
AO1
RTC in Heating mode
RehtConf = 0 (No reheat at the zone
CC2
Device closed
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
AO2 = 0 Vdc & BO5 = Off
Min Pos
if DisMinPo = Enabled
or
0 Vdc
if DisMinPo = Disabled
Temperature increase
Device opened
10 Vdc or Max Pos
Device closed
Min Pos
if DisMinPo = Enabled
AO1
Cooling
Setpoint
RTC in Cooling mode
RehtConf = 0 (No reheat at the zone)
CC1
DEAD BAND
Heating
Setpoint
AO2 = 0 Vdc & BO5 = Off
or
0 Vdc
if DisMinPo = Disabled
Temperature increase
Device opened
100% or Max Pos
Device closed
Min Pos
if DisMinPo = Enabled
BO1-BO2
Cooling
Setpoint
RTC in Cooling mode
RehtConf = 0 (No reheat at the zone)
CC1
DEAD BAND
Heating
Setpoint
BO3-BO4 = 0% & BO5 = Off
or
0%
if DisMinPo = Disabled
Temperature increase
Device opened
100% or Max Pos
BO1-BO2
RTC in Heating mode
RehtConf = 0 (No reheat at the zone)
CC2
Device closed
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
BO3-BO4 = 0% & BO5 = Off
Min Pos
if DisMinPo = Enabled
or
0%
if DisMinPo = Disabled