Specifications, Cc10, Vz7260c series: floating outputs – Viconics VZ7260X Installation Guide User Manual
Page 32

32 | VZ7260B Series - Installation Guide
RehtConf = 4 = Analog Duct Reheat & On-Off Perimeter Reheat
VZ7260F Series: Analog Outputs
VZ7260C Series: Floating Outputs
Temperature increase
Device closed
Min Pos
Cooling
Setpoint
RTC in cooling mode
RehtConf = 4 (Terminal reheat on AO2 &
Perimeter Heating on BO5)
(1) If AO2 stage is locked, AO1 = Min Pos
(2) If AO2 stage is locked, AO1 = 0Vdc
CC9
DEAD BAND
Heating
Setpoint
Device opened
Max Heat Pos (1)
AO2
Device closed
0%
Device
On
Device
Off
BO5
Device opened
100%
AO1
Device opened
10 Vdc or Max Pos
0Vdc
if DisMinPo = Disabled (2)
Temperature increase
AO1
Device
Opened 100%
Device
Closed 0%
AO2
CC10
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
RTC in Heating mode
RehtConf = 4 (Terminal reheat on AO2 &
Perimeter Heating on BO5)
Device opened
10 Vdc or Max Pos
Device
On
BO5
Device
Off
Device closed
Min Pos
if DisMinPo = Enabled
or
0 Vdc
if DisMinPo = Disabled
Temperature increase
Device closed
Min Pos
Cooling
Setpoint
RTC in cooling mode
RehtConf = 4 (Terminal reheat on BO3-BO4 &
Perimeter Heating on BO5)
(1) If BO3-BO4 stage is locked, BO1-BO2 = Min Pos
(2) If BO3-BO4 stage is locked, BO1-BO2 = 0%
CC9
DEAD BAND
Heating
Setpoint
Device opened
Max Heat Pos (1)
BO3-BO4
Device closed
0%
Device
On
Device
Off
BO5
Device opened
100%
BO1-BO2
Device opened
100% or Max Pos
0%
if DisMinPo = Disabled (2)
Temperature increase
BO1-BO2
Device
Opened 100%
Device
Closed 0%
BO3-BO4
CC10
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
RTC in Heating mode
RehtConf = 4 (Terminal reheat on BO3-BO4 & Perimeter Heating on BO5)
Device opened
100% or Max Pos
Device
On
BO5
Device
Off
Device closed
Min Pos
if DisMinPo = Enabled
or
0%
if DisMinPo = Disabled