Specifications, Cc10, Vz7260c series: floating outputs – Viconics VZ7260X Installation Guide User Manual

Page 32

background image

32 | VZ7260B Series - Installation Guide

RehtConf = 4 = Analog Duct Reheat & On-Off Perimeter Reheat

VZ7260F Series: Analog Outputs

VZ7260C Series: Floating Outputs

Temperature increase

Device closed

Min Pos

Cooling

Setpoint

RTC in cooling mode
RehtConf = 4 (Terminal reheat on AO2 &
Perimeter Heating on BO5)
(1) If AO2 stage is locked, AO1 = Min Pos
(2) If AO2 stage is locked, AO1 = 0Vdc

CC9

DEAD BAND

Heating

Setpoint

Device opened

Max Heat Pos (1)

AO2

Device closed

0%

Device

On

Device

Off

BO5

Device opened

100%

AO1

Device opened

10 Vdc or Max Pos

0Vdc

if DisMinPo = Disabled (2)

Temperature increase

AO1

Device

Opened 100%

Device

Closed 0%

AO2

CC10

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode
RehtConf = 4 (Terminal reheat on AO2 &
Perimeter Heating on BO5)

Device opened

10 Vdc or Max Pos

Device

On

BO5

Device

Off

Device closed

Min Pos

if DisMinPo = Enabled

or

0 Vdc

if DisMinPo = Disabled

Temperature increase

Device closed

Min Pos

Cooling

Setpoint

RTC in cooling mode

RehtConf = 4 (Terminal reheat on BO3-BO4 &

Perimeter Heating on BO5)

(1) If BO3-BO4 stage is locked, BO1-BO2 = Min Pos
(2) If BO3-BO4 stage is locked, BO1-BO2 = 0%

CC9

DEAD BAND

Heating

Setpoint

Device opened

Max Heat Pos (1)

BO3-BO4

Device closed

0%

Device

On

Device

Off

BO5

Device opened

100%

BO1-BO2

Device opened

100% or Max Pos

0%

if DisMinPo = Disabled (2)

Temperature increase

BO1-BO2

Device

Opened 100%

Device

Closed 0%

BO3-BO4

CC10

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode
RehtConf = 4 (Terminal reheat on BO3-BO4 & Perimeter Heating on BO5)

Device opened

100% or Max Pos

Device

On

BO5

Device

Off

Device closed

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled