23 | VZ7260B Series - Installation Guide

St-By HT

Stand-by heating setpoint

Default: 65 °F (18°C)

Stand-by heating setpoint adjustment. This setpoint will be

used if there is a motion detector connected and configured

on BI1 or a PIR sensor cover used.

Heating setpoint range is:
40 to 90 °F (4.5 to 32.0 °C)

St-By CL

Stand-by cooling setpoint limit

Default: 75 °F (24°C)

Stand-by cooling setpoint adjustment. This setpoint will be

used if there is a motion detector connected and configured

on BI1 or a PIR sensor cover used.

Cooling setpoint range is:
54 to 100 °F (12.0 to 37.5 °C)

Set Type

Temporary user setpoints

enable

Default: permnent




Enables temporary setpoints feature to any local change of

occupied setpoints.

temporar: (temporary) Any new setpoints entered by the

user will revert back to their default value after internal timer

ToccTime expires.

To change setpoints permanently, revert to No this variable

or write new setpoint values through the network. Any

setpoints written through the network will be permanent ones

and saved to permanent memory.

permnent: (permanent) Any changes of occupied setpoints
entered by the user through the keypad are permanent and
saved to permanent memory.

TOccTime

Temporary occupancy time

Default value = 2 hours




Temporary occupancy time with occupied mode setpoints

when override function is enabled.

When the controller is in unoccupied mode, function is

enabled with the local override keypad button.

Range is: 0,1, 2, 3, 4 & up to 12 hours

(Increments: 1 hr or 10 hr)

Cal RS

Room air temperature sensor

calibration

Default: 0.0 °F or °C

Offset that can be added or subtracted to actual displayed

and used room temperature

± 5.0 °F, 1.0 °F increments

(± 2.5 °C, 0.5 °C increments)

Deadband

Minimum deadband

Default: 2.0 °F (1.0 °C)

Minimum deadband value between the heating and cooling

setpoints. If modified, it will be first applied only when a

setpoint is modified.

2, 3, 4 or 5 °F, 1.0 °F increments
(1.0 to 2.5 °C, 0.5 °C increments)