Viconics VZ7260X Installation Guide User Manual
Page 28

28 | VZ7260B Series - Installation Guide
RehtConf = 1 = Analog Duct Reheat Only
VZ7260F Series: Analog Outputs
VZ7260C Series: Floating Outputs
Temperature increase
Cooling
Setpoint
RTC in cooling mode
RehtConf = 1 (Analog Duct Reht Only)
BO5 = Off
(1) If AO2 stage is locked, AO1 = Min Pos
(2) If AO2 stage is locked, AO1 = 0Vdc
DEAD BAND
Heating
Setpoint
Device closed
0%
Device opened
100%
CC3
Device closed
Min Pos
AO1
Device opened
MaxHeat Pos (1)
AO2
Device opened
10 Vdc or Max Pos
0Vdc
if DisMinPo = Disabled (2)
Temperature increase
AO1
Device
opened 100%
Device
closed 0%
AO2
CC4
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
RTC in Heating mode
RehtConf = 1 (Analog Duct Reht Only)
BO5 = Off
Device opened
10 Vdc or Max Pos
Device closed
Min Pos
if DisMinPo = Enabled
or
0 Vdc
if DisMinPo = Disabled
Temperature increase
Cooling
Setpoint
RTC in cooling mode
RehtConf = 1 (Analog Duct Reht Only)
BO5 = Off
(1) If BO3-BO4 stage is locked, BO1-BO2 = Min Pos
(2) If BO3-BO4 stage is locked, BO1-BO2 = 0%
DEAD BAND
Heating
Setpoint
Device closed
0%
Device opened
100%
CC3
Device closed
Min Pos
BO1-BO2
Device opened
MaxHeat Pos (1)
BO3-BO4
Device opened
100% or Max Pos
0%
if DisMinPo = Disabled (2)
Temperature increase
BO1-BO2
Device
opened 100%
Device
closed 0%
BO3-BO4
CC4
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
RTC in Heating mode
RehtConf = 1 (Floating Duct Reht Only)
BO5 = Off
Device opened
100% or Max Pos
Device closed
Min Pos
if DisMinPo = Enabled
or
0%
if DisMinPo = Disabled