33 | VZ7260B Series - Installation Guide

RehtConf = 5 = Pulsed Duct heater & On-Off/Pulsed perimeter reheat (All electric)

VZ7260C Series: Floating Outputs

Temperature increase

Device closed

Min Pos

Cooling

Setpoint

RTC in cooling mode

CC11b

DEAD BAND

Heating

Setpoint

Device

On

Device

Off

BO3

BO1-BO2

Device opened

100% or Max Pos

BO4

RehtConf = 5 Duct reheat on BO5 (BO5 Time = 15m) &

Perimeter Heating on BO3 (15m) and/or
BO4 (10s)

1) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =Min Pos
2) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =0%

Device opened

MaxHeat Pos (1)

BO5 Output Off

BO5 Output On

Device closed

Min Pos

if DisMinPo = Enabled or

0% if DisMinPo = Disabled (2)

Temperature increase

Device closed

Min Pos

Cooling

Setpoint

RTC in cooling mode

1) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =Min Pos
2) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =0%

CC11a

DEAD BAND

Heating

Setpoint

Device opened

Max Heat Pos (1)

BO5

Device

0%

Device

On

Device

Off

BO3

Device

100%

BO1-BO2

Device opened

100% or Max Pos

0%

if DisMinPo = Disabled

(2)

BO4

RehtConf = 5 Duct reheat on BO5 (BO5 Time = 10s) &

Perimeter Heating on BO3 (15m) and/or
BO4 (10s)

Temperature increase

BO1-BO2

CC12

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode

Device opened

100% or Max Pos

Device

On

Device

Off

Device closed

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled

BO5

BO3

Device

0%

Device

100%

BO4

RehtConf = 5 Duct reheat on BO5 &

Perimeter Heating on BO3 (15m) and/or
BO4 (10s)