33 | VZ7260B Series - Installation Guide
RehtConf = 5 = Pulsed Duct heater & On-Off/Pulsed perimeter reheat (All electric)
VZ7260C Series: Floating Outputs
Temperature increase
Device closed
Min Pos
Cooling
Setpoint
RTC in cooling mode
CC11b
DEAD BAND
Heating
Setpoint
Device
On
Device
Off
BO3
BO1-BO2
Device opened
100% or Max Pos
BO4
RehtConf = 5 Duct reheat on BO5 (BO5 Time = 15m) &
Perimeter Heating on BO3 (15m) and/or
BO4 (10s)
1) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =Min Pos
2) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =0%
Device opened
MaxHeat Pos (1)
BO5 Output Off
BO5 Output On
Device closed
Min Pos
if DisMinPo = Enabled or
0% if DisMinPo = Disabled (2)
Temperature increase
Device closed
Min Pos
Cooling
Setpoint
RTC in cooling mode
1) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =Min Pos
2) If BO5 OALK is active & DisMinPo Disabled, BO1-BO2 =0%
CC11a
DEAD BAND
Heating
Setpoint
Device opened
Max Heat Pos (1)
BO5
Device
0%
Device
On
Device
Off
BO3
Device
100%
BO1-BO2
Device opened
100% or Max Pos
0%
if DisMinPo = Disabled
(2)
BO4
RehtConf = 5 Duct reheat on BO5 (BO5 Time = 10s) &
Perimeter Heating on BO3 (15m) and/or
BO4 (10s)
Temperature increase
BO1-BO2
CC12
Cooling
Setpoint
DEAD BAND
Heating
Setpoint
RTC in Heating mode
Device opened
100% or Max Pos
Device
On
Device
Off
Device closed
Min Pos
if DisMinPo = Enabled
or
0%
if DisMinPo = Disabled
BO5
BO3
Device
0%
Device
100%
BO4
RehtConf = 5 Duct reheat on BO5 &
Perimeter Heating on BO3 (15m) and/or
BO4 (10s)