Status display


The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight that is always active and can only be seen at night.

When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the current status of the system.

Each item is scrolled sequentially with the back light in low level mode. Pressing any key
will cause the back light to come on to high level.

Manual scrolling of each menu item is achieved by pressing the Yes (scroll) key
repetitively. The last item viewed will be shown on the display for 30 seconds before
returning to automatic scrolling. Temperature is automatically updated when scrolling is
held.

Sequence of auto-scroll status display:

ROOM

TEMPERATURE

OCCUPANCY

STATUS

OUTDOOR

TEMPERATURE

RoomTemp

x.x °C or°F

Occupied

Outdoor

x.x °C or°F

Stand-By

Unoccup

Override


Outdoor air temperature

 Outdoor air temperature display is only enabled when outdoor air temperature sensor is

connected.

A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.

A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.


Occupancy Status
• Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling

display.

• Two status LED’s on the controller cover are used to indicate a call for heat or a call

for cooling

When heating & reheat is ON, the HEAT LED will illuminate

When cooling is ON, the COOL LED will illuminate