Configuring and status display instructions, Status display – Viconics VZ7260X Installation Guide User Manual
Page 13
13 | VZ7260B Series - Installation Guide
C
ONFIGURING AND
S
TATUS
D
ISPLAY
I
NSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the current status of the system.
Each item is scrolled sequentially with the back light in low level mode. Pressing any key
will cause the back light to come on to high level.
Manual scrolling of each menu item is achieved by pressing the Yes (scroll) key
repetitively. The last item viewed will be shown on the display for 30 seconds before
returning to automatic scrolling. Temperature is automatically updated when scrolling is
held.
Sequence of auto-scroll status display:
ROOM
TEMPERATURE
OCCUPANCY
STATUS
OUTDOOR
TEMPERATURE
RoomTemp
x.x °C or°F
Occupied
Outdoor
x.x °C or°F
Stand-By
Unoccup
Override
Outdoor air temperature
Outdoor air temperature display is only enabled when outdoor air temperature sensor is
connected.
•
A maximum range status display of 50 °C (122 °F) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.
•
A minimum range status -40 °C (-40 °F) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts and
economizer function are automatically disabled.
Occupancy Status
• Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling
display.
• Two status LED’s on the controller cover are used to indicate a call for heat or a call
for cooling
When heating & reheat is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate