18 | VZ7260B Series - Installation Guide

BI1

Binary input no.1
configuration

Default: None

(None): No function will be associated with the input. Point
can still be monitored through the BACnet ™ network.

(Motion NO): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.

When motion is detected at the zone, the Occupied
setpoint resumes.

Contact opened = No motion detected.

Contact closed = Motion detected.

(Motion NC): Used in Occupied Mode only to toggle from
the Occupied setpoints to the Stand-By setpoints when no
motion is detected for 60 minutes at the zone.

When motion is detected at the zone, the Occupied
setpoint resumes.

Contact opened = Motion detected.

Contact closed = No motion detected.

AI4

Analog input no.4
configuration

Default: None

(None): No function will be associated with the input. Point
can still be monitored through the BACnet network.

CO2: Used when a 0-10VDC CO2 sensor is connected to
AI4 input. The value of the input signal is displayed in AI4
Dis parameter.