22 | VZ7260B Series - Installation Guide
BO5 Time
Sets the time base for the ON-
Off reheat output if used
Default: 0 = 15 minute
Valid only if reheat sequences are enabled with BO5
0= 15 minutes
1= 10 seconds for Solid state relays
BO5 cont
BO5 contact function
Default value = 0 = NO
Enables the use of normally opened or normally closed 2
position reheat valves.
0 = NO, Energized = Contact Closed / De-energized =
Contact Opened
1 = NC, Energized = Contact Opened / De-energized =
Contact Closed
St-By TM
Stand-by Timer value
Default 0.5 hours
Time delay between the moment when the PIR cover
detected the last movement in the area and the time when
the controller’s stand-by mode and setpoints become active.
Range is: 0.5 to 24.0 hours in 0.5hr increments.
Unocc TM
Unoccupied Timer value
Default 0.0 hours
Time delay between the moment where the controller
toggles to stand-by mode and the time which the controller
unoccupied mode and setpoints become active.
The factory value or 0.0 hours: Setting this parameter to its
default value of 0.0 hours disables the unoccupied timer.
This prevents the controller to drift from stand-by mode to
unoccupied mode when PIR functions are used.
Range is: 0.0 to 24.0 hours in 0.5hr increments.
Unocc HT
Unoccupied heating setpoint
Default: 62 °F (17°C)
Unoccupied heating setpoint adjustment.
Heating setpoint range is:
40 to 90 °F (4.5 to 32.0 °C)
(Increments:0.5° or 5°)
Unocc CL
Unoccupied cooling setpoint
limit
Default: 80 °F (27°)
Unoccupied cooling setpoint adjustment.
Cooling setpoint range is:
54 to 100 °F (12.0 to 37.5 °C) (Increments: .5° or 5°)