22 | VZ7260B Series - Installation Guide

BO5 Time

Sets the time base for the ON-

Off reheat output if used

Default: 0 = 15 minute

Valid only if reheat sequences are enabled with BO5

0= 15 minutes
1=
10 seconds for Solid state relays

BO5 cont

BO5 contact function

Default value = 0 = NO

Enables the use of normally opened or normally closed 2

position reheat valves.

0 = NO, Energized = Contact Closed / De-energized =

Contact Opened
1 = NC, Energized = Contact Opened / De-energized =
Contact Closed

St-By TM

Stand-by Timer value

Default 0.5 hours

Time delay between the moment when the PIR cover
detected the last movement in the area and the time when
the controller’s stand-by mode and setpoints become active.

Range is: 0.5 to 24.0 hours in 0.5hr increments.

Unocc TM

Unoccupied Timer value

Default 0.0 hours


Time delay between the moment where the controller
toggles to stand-by mode and the time which the controller
unoccupied mode and setpoints become active.

The factory value or 0.0 hours: Setting this parameter to its
default value of 0.0 hours disables the unoccupied timer.
This prevents the controller to drift from stand-by mode to
unoccupied mode when PIR functions are used.

Range is: 0.0 to 24.0 hours in 0.5hr increments.

Unocc HT

Unoccupied heating setpoint

Default: 62 °F (17°C)

Unoccupied heating setpoint adjustment.

Heating setpoint range is:
40 to 90 °F (4.5 to 32.0 °C)

(Increments:0.5° or 5°)

Unocc CL

Unoccupied cooling setpoint

limit

Default: 80 °F (27°)

Unoccupied cooling setpoint adjustment.

Cooling setpoint range is:
54 to 100 °F (12.0 to 37.5 °C) (Increments: .5° or 5°)