Viconics VZ7260X Installation Guide User Manual
Page 16

16 | VZ7260B Series - Installation Guide
Configuration Parameters
Default Value
Significance and Adjustements
PswrdSet
Configuration parameters
menu access password
Default value = 0
No password prompted
This parameter sets a password access to prevent
unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration
menu.
Range is: 0 to 1000
Zone MAC
Zone Controller Controller
network address
Default Value: 255
RTC MAC address must be unique for the entire
network.
1 to 255 (Increments: 1 or 10)
For BACnet™ models valid range to use is from 1 to
127.
Zone Baud
RTC Controller
Communication Baud Rate
Default Value: 4 = Auto
This parameter will set the network’s baud rate.
0 = 9600 KBps
1 = 19200 KBps
2 = 38400 KBps
3 = 76800 KBps
4 = Auto Bauding (Baud Rate will match detected Baud
Rate).
Get From
Controller Get From another
device configuration utility
Default value = 255
Range is: 1 to 255
Entering a new MAC address enabled an automatic
routine that automatically fetches all the required
configuration property of the current device from another
one already configured to the same required property
values. If another value than the default value of 255 is
entered, user will then be prompted to exit the
Configuration Menu.
Ex.: If you are currently configuring MAC12 and the
settings exactly match the settings of ZN MAC5, then
enter 5 as the current parameter value.
If the process is successful and all required configuration
properties have been copied, the value will revert back to
255.
If the process is NOT successful and all required
configuration properties have NOT been copied ( either
the reference device is NOT the same model number or
is offline or does not exists ) the value will revert back to
254 to indicate the failure of the process.
Leaving the Get From parameter to 255 means that
every configuration parameters has to be set manually.
RTC MAC
RTC Controller network
address
Default: 4
Master VZ76 RTU system controller to which current
VZ72 Zone controller is attached
1 to 127 (Increments: 1 or 10)