Cc5a, Cc5b, Vz7260c series: floating outputs – Viconics VZ7260X Installation Guide User Manual

Page 30

background image

30 | VZ7260B Series - Installation Guide

VZ7260C Series: Floating Outputs

RTC in Cooling mode
RehtConf = 2 ( On/Off Duct Reht Only)
BO3-BO4 = 0%
On/Off Rht Time Base = 10 sec

(1) If BO5 stage is locked, BO1-BO2 = Min Pos

When BO5 = 0%, BO1-BO2 = Min Pos
When BO5 = 100%, BO1-BO2 = Max Pos
Otherwise, BO1-BO2 output is proportional to BO5 output

Temperature increase

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

Device closed

0%

Device opened

100%

CC5a

Device closed

Min Pos

BO1-BO2

Device opened

MaxHeat Pos (1)

BO5

Device opened

100% or Max Pos

0%

if DisMinPo = Disabled (2)

(2) If BO5 stage is locked, BO1-BO2 = 0%

When BO5 = 0%, BO1-BO2 = 0%
When BO5 = 100%, BO1-BO2 = Max Pos
Otherwise, BO1-BO2 output is proportional to BO5 output

RTC in Cooling mode
RehtConf = 2 ( On/Off Duct Reht Only)
BO3-BO4 = 0%
On/Off Rht Time Base = 15 min
(1) If BO5 stage is locked, BO1-BO2 = Min Pos

When BO5 = Off, BO1-BO2 = Min Pos
When BO5 = On, BO1-BO2 = Max Pos

Temperature increase

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

Device Off

Device On

CC5b

Device closed

Min Pos

BO1-BO2

Device opened

MaxHeat Pos (1)

BO5

Device opened

100% or Max Pos

BO5 Output Off

BO5 Output On

Device closed

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled (2)

(2) If BO5 stage is locked, BO1-BO2 = 0%

When BO5 = Off, BO1-BO2 = 0%
When BO5 = On, BO1-BO2 = Max Pos

Temperature increase

BO1-BO2

Device

On

Device

Off

BO5

CC6

Cooling

Setpoint

DEAD BAND

Heating

Setpoint

RTC in Heating mode
RehtConf = 2 (On/Off Duct Reht Only)
BO3-BO4 = Off

Device opened

100% or Max Pos

Device closed

Min Pos

if DisMinPo = Enabled

or

0%

if DisMinPo = Disabled