| PIR Ready VT7600 Series-Installation Guide

028-0363-02

Max CO

2

Maximum CO

2

Level

Default value =

1200

ppm

Maximum CO

2

Level allowed. Effective only in Occupied

mode (Fan is ON). This value is used to determine the fresh

air damper position based on the Min/Max CO

2

and Min/Max

Pos values set. See Fresh Air Damper Position section for

more details.
0 to 2000 ppm, 10 or 100 increments

MS dis

Display mixed air tem-

perature, only if sensor is

installed.

Used as diagnostic / service help to troubleshoot and diag-

nose economizer operation.

CO

2

Level

Display CO

2

Level, only

if a CO

2

transmitter is

installed at AI1 input.

Used as diagnostic / service help to troubleshoot and diag-

nose IAQ control operation