Viconics VT7606E Installation Manual User Manual
Page 25

25
| PIR Ready VT7600 Series-Installation Guide
028-0363-02
2/4event
Number of events
configuration
Default value =
2 event
2 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
4 events, will set up scheduling for the following
Event 1 is for Occupied setpoints
Event 2 is for Unoccupied setpoints
Event 3 is for Occupied setpoints
Event 4 is for Unoccupied setpoints
Prog rec
Progressive recovery
enabled
Default value =
Off
Progressive recovery is
automatically disabled
if DI 1 and / or DI 2 are
configured remote NSB
Off, = no progressive recovery
The occupied schedule time is the time at which the
system will restart.
On, = progressive recovery active.
The occupied schedule time is the time at which the de-
sired occupied temperature will be attained. The Terminal
Equipment Controller will automatically optimize the
equipment start time.
In any case, the latest a system will restart is 10 minutes
prior to the occupied period time.
Min SH
Only valid if HT Type
is set to Analog
Minimum supply heat
temperature setpoint
Default value =
64 °F
(18 °C)
Sets the minimum supply heat to be maintained by the
controller during occupied periods (Occupied or Tempo-
rary Override).
From 50 °F up to 72 °F (10 °C up to 22 °C)
(increments: 0.5° or 5°)
Chngstpt
Changeover setpoint
Default value =
55 °F
(13.0 °C)
In Cooling mode.
The outside air temperature value at which the cooling
will be switched over from mechanical (compressor) to
free cooling (economizer)
14 to 70 °F (-10.0 to 21.0 °C)