| PIR Ready VT7600 Series-Installation Guide

028-0363-02

2/4event
Number of events

configuration
Default value =

2 event

2 events, will set up scheduling for the following

Event 1 is for Occupied setpoints

Event 2 is for Unoccupied setpoints

4 events, will set up scheduling for the following

Event 1 is for Occupied setpoints

Event 2 is for Unoccupied setpoints

Event 3 is for Occupied setpoints

Event 4 is for Unoccupied setpoints

Prog rec
Progressive recovery

enabled
Default value =

Off

Progressive recovery is

automatically disabled

if DI 1 and / or DI 2 are

configured remote NSB

Off, = no progressive recovery

The occupied schedule time is the time at which the

system will restart.

On, = progressive recovery active.

The occupied schedule time is the time at which the de-

sired occupied temperature will be attained. The Terminal

Equipment Controller will automatically optimize the

equipment start time.
In any case, the latest a system will restart is 10 minutes

prior to the occupied period time.

Min SH
Only valid if HT Type

is set to Analog
Minimum supply heat

temperature setpoint
Default value =

64 °F

(18 °C)

Sets the minimum supply heat to be maintained by the

controller during occupied periods (Occupied or Tempo-

rary Override).

From 50 °F up to 72 °F (10 °C up to 22 °C)

(increments: 0.5° or 5°)

Chngstpt
Changeover setpoint
Default value =

55 °F

(13.0 °C)

In Cooling mode.
The outside air temperature value at which the cooling

will be switched over from mechanical (compressor) to

free cooling (economizer)
14 to 70 °F (-10.0 to 21.0 °C)